10 Appendix A Fuse base tables
Low-voltage fuses (fuse-links) acc. to DIN EN 60269. VDE 0636 (e.g. l.v. h.b.c.) and circuit-brea-
kers acc. to DIN EN 60898. VDE 0641
Melting times or trip-out time are depending on current-time characteristics and trip-out current
kers acc. to DIN EN 60898. VDE 0641
Melting times or trip-out time are depending on current-time characteristics and trip-out current
Fuse links are classified in utilisation categories (e.g. gL-gG)
Circuit-breakers were formerly characterised with a letter, today, the same letter is also the type
designation
The current-time characteristics (see data in the fuse base table below) are identical for fuse type
NV and gG (indicated in display) and gL-gG (entry in table)!
Fuse-link
gL
Circuit-breakers were formerly characterised with a letter, today, the same letter is also the type
designation
The current-time characteristics (see data in the fuse base table below) are identical for fuse type
NV and gG (indicated in display) and gL-gG (entry in table)!
Fuse-link
gL
=
Whole area line protection (obsolete designation)
gG
=
Whole area appliance protection (obsolete designation)
gL-gG =
Cable and line protection, discriminating characteristics
Circuit-breaker type
B
B
=
Area of instantaneous tripping 3 - 5 x I
N
C
=
Area of instantaneous tripping 5 - 10 x I
N
K
=
Area of instantaneous tripping 8 - 15 x I
N
D
=
Area of instantaneous tripping 10 - 20 x I
N