12 Appendix C Power Supply Network with Lower Voltage
12.1 Applicable standards
BS7671
12.2 Basic information
If an integrated protection against electrical accidents is required, but no safety extra-low voltage
is used, it is necessary to use specific power supply networks. For this purpose, it is possible to
use power supply networks with lower voltage and earthing.
For a nominal voltage of 110 V, two options are possible:
use power supply networks with lower voltage and earthing.
For a nominal voltage of 110 V, two options are possible:
55 V
55 V
PE
L1
L2
110 V
63 V
63 V
L1
L2
110 V
63 V
L3
110 V
110 V
- single-phase with center tap, connected
to the protective conductor (i.e. 2 x 55 V)
- three-phase star connection with center tap, con-
nected to the protective conductor (i.e. 3 x 63 V)
- no neutral conductor
- no neutral conductor
Figure 12.1: General power supply networks with lower voltage
12.3 Measuring guidelines
Before testing, the user has to select the power supply network with lower voltage in the device. To
know how to select the power supply network with lower voltage, refer to chapter 4.4.1 „Settings
of the Power Supply Network“. After having selected the power supply network with lower voltage,
the device can be used immediately. The selected power supply network remains stored in the de-
vice even if the device is switched off.
know how to select the power supply network with lower voltage, refer to chapter 4.4.1 „Settings
of the Power Supply Network“. After having selected the power supply network with lower voltage,
the device can be used immediately. The selected power supply network remains stored in the de-
vice even if the device is switched off.
The table below lists the functions of the BENNING IT 120 B intended for testing and measuring of
power supply networks. It also contains remarks on compatibility with regard to power supply net-
works with lower voltage.
power supply networks. It also contains remarks on compatibility with regard to power supply net-
works with lower voltage.
Functions for power supply net-
works with lower voltage
works with lower voltage
Remarks
Continuity test
R low-Ω
independent of the selected power supply network
continuity test
Insulation
independent of the selected power supply network
Line resistance
line resistance
resistance RL1-L2.
prospective short-circuit current
I
PSC
for U
L1-L2
= 110 V