10. Conducting tests with the TG uni 1appliance tester:
in accordance with DIN VDE 0701 and DIN VDE 0702, PC I
Connecting the test object
Connect one end of the test line to the probe socket of the tester.
Use the crocodile clip to connect the other end of the test line with a
metal part of the test object, which is connected to the protective
conductor.
Ensure that the crocodile clip makes a good contact with the metal part
of the test object.
Connect the mains plug of the test object with the test socket of the
tester.
Switch on the test object with the mains switch.
Switching on the appliance tester
Connect the mains plug of the tester to a properly connected and functional
earthed mains socket. Switch on the tester with the mains switch. Press the
large button in the Switch-on display (Fig. 12).
Entering the test date
The test date is entered or confirmed in the following display (Fig. 12a).
The tester is not equipped with a real-time clock!
Settings for measuring
Press the function button [Test procedure according to standard] in the ‘Main
menu’ (Fig. 13).
A display with the ‘Settings for measuring’ appears (Fig. 14). The standard
VDE 0701 is preset – change with the [Standard] button.
The protection class is set with the [PC] button (presetting: PC I). Selection
of the test procedure – with or without insulation resistance – is specified
with the [Ins y/n] button.
The headline shows the set measuring method for protective conductor
current [DIR.] or [DIF.] (see Point 6.3) and the setting for the manual [H] or
automatic [A] test procedure. The status line provides information about the
current settings throughout the test procedure. In the limit values line you
see the corresponding limit values.
Headline
Status line
Limit values line
Fig. 14
Fig. 12
Fig. 13
22
Operating manual for the TG uni 1 appliance tester
Conducting tests in accordance with VDE 0701 and 0702 - PC I
f
f
f
Fig. 12a
Test procedure:
- manual [H]
- automatic [A]
&
&
&
&
&