Техническая Спецификация для Conrad Energy 12V Ah lead acid battery, 250202

Модели
250202
Скачать
Страница из 2
 
 
 
CP1270
   
12V 7Ah(20hr)
 
The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid 
electrolyte is absorbed by separators and plates and thus immobilized. Should the 
battery be accidentally overcharged producing hydrogen and oxygen, special one-
way valves allow the gases to escape thus avoiding excessive pressure build-up. 
Otherwise, the battery is completely sealed and is, therefore, maintenance-free, 
leak proof and usable in any position. 
 
Battery Construction
Component
Positive plate
Negative plate
Container
Cover
Safety valve
Terminal
Separator
Electrolyte
Raw material
Lead dioxide
Lead
ABS
ABS
Rubber
Copper
F berglass
Sulfuric acid
General Features 
●     
Absorbent Glass Mat (AGM) technology 
for efficient gas recombination of up to 
99% and freedom from electrolyte 
maintenance or water adding.
●     
Not restricted for air transport-complies 
with IATA/ICAO Special Provision A67.
●     
UL-recognized component.
●     
Can be mounted in any orientation.
●     
Computer designed lead, calcium tin alloy 
grid for high power density.
●     
Long service life, float or cyclic 
applications.
●     
Maintenance-free operation.
●     
Low self discharge.
Dimensions and Weight
  Length(mm / inch)
151 / 5.94
  Width(mm / inch)
65 / 2.56
  Height(mm / inch) 
93.5 / 3.68
  Total Height(mm / inch) 
100 / 3.94
  Approx. Weight(Kg / lbs) 
2.32 / 5.12
 
 
 
 
Performance Characteristics 
Nominal Voltage
12V
Number of cell
6
Design Life 
5 years 
Nominal Capacity 77
o
F(25
o
C)
 
  20 hour rate (0.35A, 10.5V)
7Ah
  10 hour rate (0.68A, 10.5V)
6.8Ah
  5 hour rate (1.13A, 10.5V)
5.65Ah
  1 hour rate (4.56A, 9.6V)
4.56Ah
Internal Resistance
 
  Fully Charged battery 77
o
F(25
o
C)
28mOhms 
Self-Discharge
 
  3% of capacity declined per month at 20
o
C(average)
Operating Temperature Range
 
  Discharge
-20~60
o
C
  Charge 
-10~60
o
C
  Storage 
-20~60
o
C
Max. Discharge Current 77
o
F(25
o
C) 
105A(5s)
Short Circuit Current
350A
Charge Methods: Constant Voltage Charge 77
o
F(25
o
C) 
  Cycle use
          Maximum charging current
2.8A
          Temperature compensation 
-30mV/
o
C
  Standby use 
          Temperature compensation 
-20mV/
o
C
  
Discharge Constant Current (Amperes at 77
o
F25
o
C)
 
End Point 
Volts/Cell
5min 10min 15min 30min
1h
3h
5h
10h
20h
1.60V
29.1
18.4
14.8
8.30
4.56
1.84
1.26
0.70 0.363
1.65V
27.5
17.5
14.2
7.90
4.40
1.80
1.22
0.69 0.359
1.70V
26.0
16.7
13.6
7.62
4.22
1.74
1.17
0.69 0.355
1.75V
24.4
15.7
13.0
7.24
4.04
1.68
1.13
0.68 0.350
1.80V
22.8
14.8
12.4
7.03
3.84
1.63
1.08
0.66 0.344
Discharge Constant Power (Watts at 77
o
F25
o
C)
 
End Point 
Volts/Cell
5min 10min 15min 30min 45min
1h
2h
3h
5h
1.60V
52.0
35.1
27.5
15.2 11.50 8.97
5.06
3.59
2.33
1.65V
49.4
33.3
26.5
14.6 11.00 8.59
4.94
3.50
2.29
1.70V
46.9
31.6
25.4
14.0 10.50 8.23
4.80
3.40
2.25
1.75V
44.5
29.8
24.3
13.4 10.10 7.99
4.65
3.30
2.21
1.80V
41.6
28.0
23.3
12.9
9.75
7.62
4.50
3.19
2.15
 
page1 of 2
 
 
(Note)The above characteristics data are average values obtained within 
three charge/discharge cycles not the mimimum values.
93.5±1
2.30-2.35VPC
2.23-2.27VPC