—    Recharge amount 1.1 1.2 times of the discharged capacity upper level of recharge amount 
is selected when ambient temp. below 5 . If discharge capacity is not sure, recharge the 
batteries as table four  
               Table four   
Ambient temp.
 
Charging voltage
V/cell  
Charging time h  
2.31 7 
2.46 4 
2.25 7 
20 
2.40 4 
2.21 7 
35 
2.34 4 
&       Note  
1 Charging time in table four means charging period after voltage reach the specified value, 
initial max. current is less than 0.03C. 
2 Follow above charging specifications, otherwise batteries will be overcharged or 
undercharged, service life of batteries will shorten.  
3 Charge the batteries as per cyclic charging parameters after capacity test discharge. 
  
 Cautions 
—    Measure the output voltage of equipment once every 2 hours for new installations for the 
initial 72 hours, to make sure the stable output of charging voltage. The output voltage 
should also be confirmed during yearly maintenance check preventing the deviations due to 
aging. 
—     If a current value at final charging stage is over 0.05C
10
A, damage on battery service life 
may occurred. 
—     For cycle charging, timer is recommended to switchover to trickle charging mode, 
preventing over-charging.  
—     For temperature other than 25
charge voltage setting need to be compensated as 
formula  
U
T
U
25
-K× T-25
T—actual temperature K—compensation coefficient  
—     Judging on completion of charging 
When one of the following conditions occurs, charging is considered be completed. 
1 Charging amount reaches 1.1 1.2 times of discharged value. 
2 Charging current is less than 0.005C
10
A at final stage of charging. 
3 Charging current keeps stable for 3 hours.