Техническая Спецификация для Phoenix Contact Distributed I/O device FLM DIO 8/4 M8-2MBD 2773568 2773568

Модели
2773568
Скачать
Страница из 11
Nov 14, 2013    2 / 11
Technical data
Ambient conditions
Degree of protection
IP65/67
General
Weight
144 g
Mounting type
Wall mounting
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
To I/O 500 V AC
Interfaces
Name
Fieldline local bus
Connection method
M8 connector
Designation connection point
Copper cable
Transmission speed
2 MBit/s
Number of positions
4
Power supply for module electronics
Connection method
M8 connector
Name
U
L
Number of positions
4
Supply voltage
24 V DC
Supply voltage range
18 V DC ... 30 V DC IEC 61131-2 (including ripple)
Supply current
3 A
Fieldline potentials
Voltage supply U
L
24 V DC
Digital inputs
Input name
Digital inputs
Connection method
M8 connector
Connection method
2, 3-wire
Number of inputs
8 (4 fixed, 4 freely selectable)
Protective circuit
Protection against polarity reversal
Filter time
3 ms
Input characteristic curve
IEC 61131-2 type 1
Input voltage
24 V DC
Input voltage range "0" signal
-30 V DC ... 5 V DC
Input voltage range "1" signal
13 V DC ... 30 V DC
Digital outputs
Output name
Digital outputs
Connection method
M8 connector
Connection method
2, 3-wire
Number of outputs
4 (Can also be used as an input)
Protective circuit
Short-circuit protection
Output voltage
24 V DC