Техническая Спецификация для Phoenix Contact Solid-state relay module PLC-OSC- 24DC/230AC/ 2/ACT 2982760 2982760

Модели
2982760
Скачать
Страница из 10
Nov 9, 2013    2 / 10
Technical data
Input data
Protective circuit/component
Damping diode
Transmission frequency
10 Hz
Output data
Output nominal voltage
230 V AC
Output voltage range
24 V AC ... 253 V AC
Limiting continuous current
2 A (see derating curve)
Maximum inrush current
30 A (10 ms)
Min. load current
25 mA
Leakage current
typ. 1 mA
Surge current
30 A (tp = 10 ms)
Max. load value
4 A
2
s (tp = 10 ms, at 25 °C)
Peak offstate voltage
600 V
Voltage drop at max. limiting continuous current
≤ 1 V
Output circuit
2-conductor floating, zero voltage switch
Type of protection
Surge protection
Connection data
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
26
Conductor cross section AWG/kcmil max
14
General
Test voltage input/output
2.5 kV (50 Hz, 1 min.)
Mounting position
see to derating
Assembly instructions
In rows with zero spacing
Operating mode
100% operating factor
Inflammability class according to UL 94
V0
Name
Standards/regulations
Standards/regulations
IEC 60664
Standards/regulations
EN 50178
Standards/regulations
IEC 62103
Rated surge voltage / insulation
Basic insulation
Pollution degree
2
Surge voltage category
III