Техническая Спецификация для Finder Overvoltage protection for sub-distribution 3-phased overvoltage suppressor IP20 7P.23.8.275.1020
Модели
7P.23.8.275.1020
•
SPD Type 1+2
•
Combination of varistor and
encapsulated spark gap
encapsulated spark gap
•
Visual fault and remote contact
fault signalling varistor/GDT status
fault signalling varistor/GDT status
•
Upside down mounting possible
•
Replaceable modules
1
7P.09.1.255.0100
7P.01.8.260.1025
7P.02.8.260.1025
•
SPD Type 1
•
Spark gap module for N-PE
application in three phase
system, 3+1 configuration
application in three phase
system, 3+1 configuration
•
Remote contact signalling
GDT presence
GDT presence
•
Upside down mounting possible
•
Replaceable modules
SPD specification
Nominal voltage (U
N
)
V AC
Maximum operating voltage (U
C
)
V AC
Lightning impulse current (10/350 μs) (I
imp
) kA
Nominal discharge current (8/20 μs) (I
n
)
kA
Maximum discharge current (8/20 μs) (I
max
)kA
Voltage protection level (U
P
)
kV
Ability to independently switch off the
following current (I
fi
)
A
Response time (t
a
)
ns
Short-circuit proof at maximum overcurrent protection kA
rms
Maximum overcurrent protection
Maximum overcurrent protection for serial connection
Replacement modules code
Other technical data
Ambient temperature range
°C
Protection degree
Wire size
mm
2
AWG
Wire strip length
mm
Screw torque
Nm
Remote status signalling contact specification
Contact configuration
Rated current
A AC/DC
Rated voltage
V AC/DC
Wire size (07P.01)
mm
2
AWG
Approvals (according to type)
Features
SPD Type 1+2 Surge arrester range - single phase
high discharge capability and without following
current - system / three phase system
•
Surge arresters, suitable for low-voltage applications,
to protect equipment against overvoltage by direct
lightning strike, induction overvoltage and
switching overvoltage
•
To be installed at the boundary of LPZ 0 - LPZ 1 zones or higher
•
Versions with combined high energy varistor
block and heavy duty encapsulated spark gap (GDT)
which eliminates leakage current and ensures
high discharge current
•
No follow current
•
Very low residual voltage
•
Low U
p
voltage
•
Replaceable modules
•
Upside down mounting possible (thanks to dual
terminal markings and new restraint system for
the replaceable module that permits its inversion)
•
Visual fault signalling: Healty/Replace
•
Double screw terminal
•
Remote status signalling contact:
Healty/Replace/Presence. Connector 07P.01 included
•
According to EN 61 643-11
•
35 mm rail EN 60715 mounting, 36mm each pole
7P.09.1.255.0100 SPD Type 1, GDT protection for
N-PE application only, for 3+1
configuration
7P.01.8.260.1025 SPD Type 1+2, varistor + GDT
unipolar protection suitable to
realize single phase or three
phase systems (230/400 V)
with the GDT protection module
(7P.09)
7P.02.8.260.1025 SPD Type 1+2 for single phase
system. Varistor + GDT protection
L-N + GDT protection N-PE
7P Series - Surge Protection Device (SPD)
N-PE
L-N
N-PE
—
230
230
—
255
260
260
255
100
25
25
50
100
30
30
50
100
60
60
100
1.5
1.5
1.5
1.5
100
No following
No following
100
current
current
100
100
100
100
—
50
50
—
—
250 A gL/gG
250 A gL/gG
—
—
125 A gL/gG
125 A gL/gG
—
7P.00.1.000.0100
7P.00.8.260.0025
7P.00.8.260.0025 7P.00.1.000.0050
–40...+80
IP20
solid cable
stranded cable
1X2.5...1x50
1X2.5...1x35
1X13...1x1
1X13...1x2
11
4
1 CO (SPDT)
1 CO (SPDT)
1 CO (SPDT)
0.5 - 0.1
0.5 - 0.1
0.5 - 0.1
250
250
250
solid cable
stranded cable
solid cable
stranded cable
solid cable
stranded cable
1.5
1.5
1.5
1.5
1.5
1.5
16
16
16
16
16
16
For outline drawing see page 11
•
SPD Type 1+2
•
Combination of varistor and
encapsulated spark gap
encapsulated spark gap
•
Visual fault and remote contact
fault signalling varistor/GDT status,
N-PE GDT presence
fault signalling varistor/GDT status,
N-PE GDT presence
•
Upside down mounting possible
•
Replaceable modules
XII-2012, www
.finder
net.com