Here  you  have  the  opportunity  to  define  a  suppressed  measurement  range.  This 
sometimes  is  needed  for  any  meters  which  do  not  start  their  measurement  range 
with 0 V or mA. If you define a suppressed measurement with 20%, then the value 0 
will is set until the current exceeds 4 mA (if a module with 0- 20 mA input is used).  
 
Please  note:  Using  a  suppressed  measurement  range  only  the  indication  of  the 
measurement  is changed.  However,  there  is no  repercussion  to  the  values  of  “Min” 
and “Max”. This definition lasts unchanged. 
 
<3e> Lower limit value & Upper limit value 
As an additional feature it is possible to put the values of 0% and 100% of the meas-
urement  range  (as  example  0-  10  Volts)  on  deliberate  numerical  values.  to  adapt 
your sensor to the initial voltage range. Now – as an example – you can define 
0% as 0 of and 100% as 500 of any unit you had choosen.
  
 
Please note: The upper limit value is possible up to a worth of 1.000.000. You have 
to enter the worth WITHOUT the dots. 
 
Example: 
Let´s assume, the choosen unit would be deg. Centigrade and the input of your GSM 
module would range from 0- 100 % resp. 0- 10 Volts. By using the upper and lower 
value to 0 and 500 the resulting indication of the measurement would range from 0 to 
500 deg. Centigrade. With choosing 20% and 50% for “Min” and “Max” the frame for 
"1" would range from 2 to 5 Volts resp. 100 to 250 deg. Centigrade. 
 
 
The software does not accept invalid combinations of Min and 
Max or upper and lower value. 
 
Since a part of the measure range can be suppressed, you can vary the output val-
ues from the same input signal as shown below: