Here you have the opportunity to define a suppressed measurement range. This
sometimes is needed for any meters which do not start their measurement range
with 0 V or mA. If you define a suppressed measurement with 20%, then the value 0
will is set until the current exceeds 4 mA (if a module with 0- 20 mA input is used).
Please note: Using a suppressed measurement range only the indication of the
measurement is changed. However, there is no repercussion to the values of “Min”
and “Max”. This definition lasts unchanged.
<3e> Lower limit value & Upper limit value
As an additional feature it is possible to put the values of 0% and 100% of the meas-
urement range (as example 0- 10 Volts) on deliberate numerical values. to adapt
your sensor to the initial voltage range. Now – as an example – you can define
0% as 0 of and 100% as 500 of any unit you had choosen.
Please note: The upper limit value is possible up to a worth of 1.000.000. You have
to enter the worth WITHOUT the dots.
Example:
Let´s assume, the choosen unit would be deg. Centigrade and the input of your GSM
module would range from 0- 100 % resp. 0- 10 Volts. By using the upper and lower
value to 0 and 500 the resulting indication of the measurement would range from 0 to
500 deg. Centigrade. With choosing 20% and 50% for “Min” and “Max” the frame for
"1" would range from 2 to 5 Volts resp. 100 to 250 deg. Centigrade.
The software does not accept invalid combinations of Min and
Max or upper and lower value.
Since a part of the measure range can be suppressed, you can vary the output val-
ues from the same input signal as shown below: