Техническая Спецификация для Panasonic AKT7111100J Digital Temperature Controller AKT7111100J

Модели
AKT7111100J
Скачать
Страница из 20
2
KT Series
Overview
Common Features
A
Multi-input: Versatile thermocouple, RTD, DC Current, DC Voltage
A
Control modes: PID, on/off control, Anti-Reset-Windup (ARW)
A
Control output: Relay, non-contact voltage output 
(for SSR drive, DC current output)
A
Accuracy: ± 0.2% span
A
Simple operation
A
Heater-burn-out alarm available
A
Alarm output with 9 different operation modes
A
RS485 ASCII/Modbus communication available
A
Supply voltage: 24V AC/DC or 100 to 240V AC
A
Compliant with UL, CSA standards and CE marking
KT4
KT9
KT8
KT7
Output method
Characteristics
Relay contact output is used for switching up to 
Relay contact output
3A 250V AC (resistive load) in applications in which 
the on-off frequency is low.
This voltage output is used for driving the SSR . Since
Voltage output for SSR drive
the SSR is a semiconductor relay, contact life is long.
This type is used in applications in which the on-off 
frequency is high. Up to 40mA 12V DC can be switched.
This current output is used to control a power regula-
DC current output
tor. Smooth and accurate control is possible because 
phase control corresponds to the current output.
KT2
Output Methods:
KT4H
Multi-input:
A
Thermocouples K, J, R, S, B, E, T, N, PL-II, C(W/Re5-26)
A
RTD Pt100, JPt100, 3-conductor system
A
DC current 0/4 - 20mA
A
DC Voltage 0 to 1V, 0 to 5V, 1 to 5V, 0 to 10V
Application examples:
Constant
temperature bath
Scrubber
Shrink wrapping 
machine
Oven
Warm and cold
storage units
08/2006