3.4 Getting started with project creation
LOGO!Soft Comfort Online Help
Operating Instructions, 06/2014
Operating Instructions, 06/2014
163
Configuring remote connections
Follow the same approach to configure remote connections as that in section Configuring
Ethernet connection, LOGO! to local LOGO! (Page 157). Note that LOGO!Soft Comfort
allows you to switch to the diagram of the connected device simply by clicking on the values
(NI1/NQ1...) in the connection dialog. This operation is only available for network blocks.
3.4.3.3
Configuring Ethernet connection, LOGO! to LOGO! slave
LOGO!Soft Comfort supports the connection of a LOGO! Base Module to a LOGO! slave
only through network blocks.
Switch the target device to slave mode. Refer to Tools -> Transfer -> Configure Master/Slave
Switch the target device to slave mode. Refer to Tools -> Transfer -> Configure Master/Slave
Mode (0BA7 and 0BA8 only) (Page 79) for details.
Follow the same steps as Configuring Ethernet connection, LOGO! to remote devices
Follow the same steps as Configuring Ethernet connection, LOGO! to remote devices
(Page 161).
Choose the target device and LOGO!Soft Comfort automatically changes the device type to
Choose the target device and LOGO!Soft Comfort automatically changes the device type to
slave.
Note
You can only create connections between a LOGO! Base Module and its client using
You can only create connections between a LOGO! Base Module and its client using
network function blocks (NI/NQ/NAI/NAQ). Drag-and-drop operations are not available in this
case.
Note
LOGO! 0BA8 supports 24 NIs and 20 NQs separately. But no matter NI or NQ, you can have
LOGO! 0BA8 supports 24 NIs and 20 NQs separately. But no matter NI or NQ, you can have
maximum 32 data connections in total.