Sample applications 
 
4.1 Air-conditioning system 
 
LOGO!Soft Comfort Online Help 
182
 
Operating Instructions, 06/2014 
●  The fresh-air fan may only be switched on if the flow sensor signals the safe operational 
state of the extractor fan. 
●  A warning lamp indicates failure of one of the fans. 
Standard solution 
The fans are under monitoring by means of flow sensors. If the sensors registered no air flow 
after a short delay time has expired, the system is switched off and an error message is 
generated, which can be acknowledged by pressing the off button. 
Fan monitoring requires an analyzer circuit with several switching devices, in addition to the 
flow sensors. A single LOGO! device can replace this analyzer circuit. 
LOGO!Soft Comfort solution 
The use of LOGO! reduces the amount of switchgear. Thus, you save installation time and 
space in the control cabinet. You may even be able to use as a smaller control cabinet. 
With LOGO! you can also switch off the fans sequentially after the system is switched off. 
The circuit in LOGO!Soft Comfort 
The system is switched on and off at the inputs I1 and I2. The fans are connected to outputs 
Q1 and Q2, the flow sensors are connected to the inputs I3 and I4. Blocks B007 and B008 
are used to set the watchdog times after which the flow sensors should send a signal to the 
fault output Q3.