5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
250
 
Operating Instructions, 06/2014 
Input Ral 
A positive edge at input Ral (Reset all) resets the hours counter (OT) and the 
output, and sets the time-to-go value (MN) to the configured maintenance 
interval (MI): 
• 
Output Q = 0 
• 
The measured operating hours OT = 0 
• 
The time-to-go of the maintenance interval MN = MI. 
Parameter 
MI: Maintenance interval to be specified in units of hours and minutes 
Range of values: 0000 h to 9999 h, 0 m to 59 m 
OT: Accumulated total operating time. An offset start time can be specified in 
hours and minutes. 
Range of values: 00000 h to 99999 h, 0 m to 59 m 
Q → 0: 
• 
When "R" is selected: 
Q = 1, if MN = 0; 
Q = 0, if R = 1 or Ral = 1 
• 
When "R+En" is selected: 
Q = 1, if MN = 0; 
Q = 0, if R = 1 or Ral = 1 or En = 0. 
Output Q 
The output is set when the time-to-go MN = 0. The output is reset: 
• 
When "Q → 0:R+En", 
if R = 1 or Ral = 1 or En = 0 
• 
When "Q → 0:R",  
if R = 1 or Ral = 1. 
Parameter MI 
The maintenance interval MI can be provided by the actual value of another already-
programmed function:  
●  Analog comparator: Ax - Ay 
●  Analog threshold trigger: Ax 
●  Analog amplifier: Ax 
●  Analog multiplexer: AQ 
●  Analog ramp: AQ 
●  Mathematic instruction: AQ 
●  PI controller: AQ 
●  Up/Down counter: Cnt 
For the 0BA7 and 0BA8 devices, you can additionally use the actual values of the following 
already-programmed functions: 
●  On-delay: Ta 
●  Off-delay: Ta 
●  On-/off-delay: Ta 
●  Retentive on-delay: Ta