Техническая Спецификация для Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8
Модели
6ED1057-3BA00-0AA8
Reference material
5.3 Special functions
LOGO!Soft Comfort Online Help
Operating Instructions, 06/2014
Operating Instructions, 06/2014
281
Input Ax
Input Ax is one of the following analog signals:
•
•
AI1 to AI8 (*)
•
AM1 to AM16 (if 0BA7), or AM1 to AM64 (if 0BA8)
•
NAI1 to NAI32
•
AQ1 to AQ2 (if 0BA7), or AQ1 to AQ8 (if 0BA8)
•
NAQ1 to NAQ16
•
Block number of a function with analog output
Parameter
Mode
Possible settings: 0, 1, 2, 3
Mode = 0: AQ = Min
Mode = 1: AQ = Max
Mode = 2 and S1= 0 (low): AQ = Min
Mode = 2 and S1= 1 (high): AQ = Max
Mode = 3 or a block value is referenced: AQ = Ax
Possible settings: 0, 1, 2, 3
Mode = 0: AQ = Min
Mode = 1: AQ = Max
Mode = 2 and S1= 0 (low): AQ = Min
Mode = 2 and S1= 1 (high): AQ = Max
Mode = 3 or a block value is referenced: AQ = Ax
Output AQ
AQ ouptuts a minimum, maximum, or actual value depending on the inputs, or is
reset to 0 if configured to do so when function is disabled
* AI1 to AI8: 0 to 10 V corresponds with 0 to 1000 (internal value).
Parameter Mode
You can set the values for parameter Mode based on the actual values of another already-
programmed function:
● Analog comparator: Ax - Ay
● Analog threshold trigger: Ax
● Analog amplifier: Ax
● Analog multiplexer: AQ
● Analog ramp: AQ
● Mathematic instruction: AQ
● Up/Down counter: Cnt
● Threshold trigger: Fre
● Max/Min: Ax
● PI controller: AQ
● Analog filter (0BA7 only): AQ
● Average value (0BA7 only): AQ
● On-delay: Ta
● Off-delay: Ta
● On-/Off-delay: Ta
● Retentative on-delay: Ta
● Wiping relay (pulse output): Ta
● Analog comparator: Ax - Ay
● Analog threshold trigger: Ax
● Analog amplifier: Ax
● Analog multiplexer: AQ
● Analog ramp: AQ
● Mathematic instruction: AQ
● Up/Down counter: Cnt
● Threshold trigger: Fre
● Max/Min: Ax
● PI controller: AQ
● Analog filter (0BA7 only): AQ
● Average value (0BA7 only): AQ
● On-delay: Ta
● Off-delay: Ta
● On-/Off-delay: Ta
● Retentative on-delay: Ta
● Wiping relay (pulse output): Ta