5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
281
 
Input Ax 
Input Ax is one of the following analog signals:  
• 
AI1 to AI8 (*) 
• 
AM1 to AM16 (if 0BA7), or AM1 to AM64 (if 0BA8) 
• 
NAI1 to NAI32 
• 
AQ1 to AQ2 (if 0BA7), or AQ1 to AQ8 (if 0BA8) 
• 
NAQ1 to NAQ16 
• 
Block number of a function with analog output 
Parameter 
Mode 
Possible settings: 0, 1, 2, 3 
Mode = 0: AQ = Min 
Mode = 1: AQ = Max 
Mode = 2 and S1= 0 (low): AQ = Min  
Mode = 2 and S1= 1 (high): AQ = Max 
Mode = 3 or a block value is referenced: AQ = Ax 
Output AQ 
AQ ouptuts a minimum, maximum, or actual value depending on the inputs, or is 
reset to 0 if configured to do so when function is disabled 
* AI1 to AI8: 0 to 10 V corresponds with 0 to 1000 (internal value). 
Parameter Mode 
You can set the values for parameter Mode based on the actual values of another already-
programmed function: 
●  Analog comparator: Ax - Ay 
●  Analog threshold trigger: Ax 
●  Analog amplifier: Ax 
●  Analog multiplexer: AQ 
●  Analog ramp: AQ 
●  Mathematic instruction: AQ 
●  Up/Down counter: Cnt 
●  Threshold trigger: Fre 
●  Max/Min: Ax 
●  PI controller: AQ 
●  Analog filter (0BA7 only): AQ 
●  Average value (0BA7 only): AQ 
●  On-delay: Ta 
●  Off-delay: Ta 
●  On-/Off-delay: Ta 
●  Retentative on-delay: Ta 
●  Wiping relay (pulse output): Ta