Техническая Спецификация для Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8

Модели
6ED1057-3BA00-0AA8
Скачать
Страница из 344
 
Programming LOGO! 
 
3.8 Configuring additional functions for LOGO! 
LOGO! 
Manual, 06/2014, A5E33039675 
103
 
●  Network digital outputs: NQ1 to NQ64 
●  Network analog outputs: NAQ1 to NAQ16 
3.8.5 
Changing LOGO! to master/slave mode 
LOGO! 0BA8 provides a menu command for network communication settings. This section 
shows you how to change LOGO!'s network communication mode.  
A LOGO! 0BA8 device works in either master or slave communication mode.  
Master mode versus slave mode 
A LOGO! 0BA8 in master mode supports client-server communication with SIMATIC S7 
PLCs, a SIMATIC HMI or other 0BA8 devices across Ethernet. This LOGO! can additionally 
act as a master to communicate with one or more 0BA8 devices in slave mode.  
A LOGO! in slave mode functions as a LOGO! expansion module. LOGO! slave devices do 
not require a circuit program. A master LOGO! can read one or more slave LOGO!'s 
digital/analog input/output values and write its own digital/analog output values to these 
slaves. This helps LOGO! achieve network I/O expansion.  
 
 
Note 
A LOGO! in slave mode can also have its own expansion modules. It also supports a 
maximum of 24 digital inputs, 8 analog inputs, 20 digital outputs and 8 analog outputs.  
 
Changing LOGO! from master mode to slave mode 
1.  In the main menu in programming mode, move the cursor to "
": Press   or   
 
2.  Confirm "
": Press OK 
3.  Move the cursor to "
": Press   or   
 
4.  Confirm "
": Press OK