LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 06/2014, A5E33039675 
141
 
●  Edge-triggered wiping relay (Page 148) (current time Ta) 
●  Asynchronous pulse generator (Page 150) (current time Ta) 
●  Stairway lighting switch (Page 154) (current time Ta) 
●  Multiple function switch (Page 156) (current time Ta) 
●  Stopwatch (Page 171) (actual value AQ) 
●  Threshold trigger (Page 180) (actual value Fre) 
Select the required function by the block number. The timebase is configurable. For 
information on valid timebase ranges and parameter preset, refer to Section "On-delay 
(Page 136)". 
Timing diagram 
 
Functional description 
LOGO! sets Output Q to hi immediately when the input Trg changes to hi. 
LOGO! retriggers the actual time T
a
 at the 1 to 0 transition of Trg. The output remains set. 
LOGO! resets Output Q to 0 with off-delay when T
a
 reaches the value configured at T (T
a
=T). 
LOGO! retriggers he time T
a
 with a one-shot at input Trg. 
You can set input R (Reset) to reset the time T
a
 and the output before T
a
 expires. 
If the block is retentive, LOGO! resets output Q and the expired time to the values before a 
power failure; if the block is not retentive, LOGO! resets output Q and the expired time to 
defaults after a power failure.