LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
176
 
Manual, 06/2014, A5E33039675 
4.4.16 
Hours counter 
Short description 
A configured time is triggered with a signal at the monitoring input. The output is set when 
this time has expired.  
 
Symbol in LOGO! 
Wiring 
Description 
 
Input R 
A positive edge (0 to 1 transition) at input R resets 
output Q and sets a configured value MI at the 
counter for the duration of the time-to-go (MN). 
Input En 
En is the monitoring input. LOGO! scans the on-time 
of this input. 
Input Ral  
A positive edge at input Ral (Reset all) resets the 
hours counter (OT) and the output, and sets the time-
to-go value (MN) to the maintenance interval MI: 
• 
Output Q = 0 
• 
Measured operating time OT = 0 
• 
Time-to-go of the maintenance interval MN = MI. 
Parameter 
MI: Maintenance interval to be preset in units of hours 
and minutes 
Range of values: 
0000 h to 9999 h, 0 m to 59 m 
OT: the accumulated total operating time (you can 
specify an offset in hours and minute) 
Range of values: 
00000 h to 99999 h, 0 m to 59 m 
Q → 0 occurs depending on the following conditions:  
• 
When "R" is selected: 
Q = 1, if MN = 0; 
Q = 0, if R = 1 or Ral = 1 
• 
When "R+En" is selected: 
Q = 1, if MN = 0; 
Q = 0, if R = 1 or Ral = 1 or En = 0. 
Output Q 
The output is set when the time-to-go MN = 0 (see 
timing diagram). 
The output is reset under the following conditions: 
• 
When "Q→0:R+En", if  
R = 1 or Ral = 1 or En = 0 
• 
When "Q→0:R", if R = 1 or Ral = 1. 
 
 
 
Note 
MI, MN and OT are always retentive.