LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
216
 
Manual, 06/2014, A5E33039675 
4.4.29 
Analog ramp 
Short description 
This function allows the output to be changed from the current level to the selected level at a 
specified rate.  
 
Symbol in LOGO! 
Wiring 
Description 
 
Input En 
A change in the status from 0 to 1 at input En 
(Enable) applies the start/stop level (Offset "B" + 
StSp) to the output for 100 ms and starts the ramp 
operation to the selected level. 
A change in the status from 1 to 0 immediately sets 
the current level to Offset "B", which makes output 
AQ equal to 0. 
Input Sel 
SeI = 0: level 1 is selected. 
SeI = 1: level 2 is selected. 
A change in status of Sel causes the current level to 
start changing to the selected level at the specified 
rate. 
Input St 
A change in the status from 0 to 1 at input St 
(Decelerated Stop) causes the current level to 
decrease at a constant rate until the start/stop level 
(Offset "B" + StSp) is reached. The start/stop level is 
maintained for 100 ms and then the current level is 
set to Offset "B", which makes output AQ equal to 0.