Technical data 
 
A.7 Technical data: LOGO! DM8 24R and LOGO! DM16 24R 
 
LOGO! 
304
 
Manual, 06/2014, A5E33039675 
 
LOGO! DM8 24R 
LOGO! DM16 24R 
Power consumption 
• 
24 VAC 
• 
24 VDC 
 
• 
20 mA to 100 mA 
• 
8 mA to 50 mA 
 
• 
- - 
• 
15 mA to 65 mA 
Voltage failure buffering 
Typ. 5 ms 
Typ. 5 ms 
Power loss 
• 
24 VAC 
• 
24 VDC 
 
• 
0.5 W to 2.4 W 
• 
0.2 W to 1.2 W 
 
• 
- - 
• 
0.35 W to 1.6 W 
Digital inputs 
Number 
4, optional positive voltage or 
negative voltage 
Electrical isolation 
No 
No 
Number of high speed inputs 
Input frequency 
• 
Normal input 
• 
High speed input 
 
• 
Max. 4 Hz 
• 
- - 
 
• 
Max. 4 Hz 
• 
- - 
Max. continuous permissible 
voltage 
• 
26.4 VAC 
• 
28.8 VDC 
• 
- - 
• 
28.8 VDC 
Input voltage  
• 
Signal 0 
• 
Signal 1 

• 
< 5 VAC/VDC 
• 
> 12 VAC/VDC 
 
• 
< 5 VDC 
• 
> 12 VDC 
Input current at 
• 
Signal 0 
• 
Signal 1 
 
• 
< 1.1 mA 
• 
> 2.63 mA 
 
• 
< 0.85 mA 
• 
> 2.0 mA 
Delay time at  
• 
0 to 1 
• 
1 to 0 
 
• 
Typ. 1.5 ms 
• 
Typ. 15 ms 
 
• 
Typ. 1.5 ms 
• 
Typ. 1.5 ms 
Line length (unshielded) 
Max. 100 m 
Max. 100 m 
Digital outputs 
Number 
Output type 
Relay outputs 
Relay outputs 
Electrical isolation 
Yes 
Yes 
In groups of 
Control of a digital input 
Yes 
Yes 
Continuous current I
th
 
Recommended range of 
application ≥ 100 mA at 
12 VAC/VDC 
Max. 5 A per relay 
Recommended range of 
application ≥ 100 mA at 
12 VAC/VDC 
Max. 5 A per relay 
Surge current 
Max. 30 A 
Max. 30 A 
Incandescent lamp load (25000 
switching cycles) at 
1000 W 
1000 W