Техническая Спецификация для Phoenix Contact Inline terminal IB IL 24 DI 8-2MBD-PAC 2861690 2861690

Модели
2861690
Скачать
Страница из 8
Nov 14, 2013    2 / 8
Technical data
Ambient conditions
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
General
Weight
118 g
Note on weight specifications
Without plug
Mounting type
DIN rail
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
Test section
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
Test section
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
Test section
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Interfaces
Fieldbus system
Lokalbus
Name
Inline local bus
Connection method
Inline data jumper
Transmission speed
2 MBit/s
Power supply for module electronics
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply current
85 mA
Communications power U
L
7.5 V (via voltage jumper)
Current consumption
max. 50 mA (from the local bus)
Inline potentials
Communications power U
L
7.5 V DC
Current consumption from U
L
max. 50 mA
Main circuit supply U
M
24 V DC
Current consumption from U
M
max. 8 A DC
Segment supply voltage U
S
24 V DC (nominal value)
Current consumption from U
S
max. 2 A
Digital inputs
Input name
Digital inputs
Connection method
Spring-cage connection
Connection method
2, 3, 4-wire
Number of inputs
8 (EN 61131-2 type 1)
Typical response time
< 1 ms
Protective circuit
Short-circuit and overload protection
Input voltage
24 V DC (via voltage jumper)
Input voltage range "0" signal
-3 V DC ... 5 V DC