4.1. Visualization - LEDs status
The hybrid motor starter visualizes the operating modes with four LEDs. The functions of the LEDs are 
oriented towards the NAMUR recommendation NE 44. 
• The general device status is displayed by a green LED (PWR). 
• The activation
 
of the drive is displayed using a yellow LED (ON).
• An internal or external error (process error: overcurrent, asymmetry, phase failure) is indicated by a red 
LED (ERR). 
After the control supply voltage is applied, all LEDs light up once as an LED test.
4.2. Diagnostics function 
Thanks to the diagnostics functions, the hybrid motor starter is in a condition to identify several internal 
errors as well as external errors (errors in the I/O). 
• If an error is detected, the device is switched to a safe switch-off mode.
• All internal errors cannot be acknowledged and are saved in the device. The device then cannot be 
operated. 
• In the case of external errors, an error acknowledgment is required to exit the safe switch-off mode.
Explanation:
= LED switched off / E = LED permanently lit / B = LED flashes approx. 2 Hz (50:50)
1)
 
Bridge between the terminals "RES" and "AUT" / 
2)
 No other measures necessary
Status
Description
LED: PWR ERR ladj ON Error acknow-
ledgement
Green Red
Yellow
Off
No supply voltage (control supply voltage) 
present
A
A
A
A
-
Readiness
 
for operation
Supply voltage (control supply voltage) present
E
A
A
A
-
Drive switched on
E
A
A
E
Internal error
Internal device error -
 
Device replacement required
E
E
A
A
Not possible
External error 
in activation or I/O 
 
(maintenance 
requirement, 
NE44)
Bimetal function: 
 
The motor current is greater than the nominal 
motor current specification (e.g. class 10 A): 
Cooling time on! (20 minutes)
E
B
A
E
Automatic 
1)
"ON" flashes after 2 minutes:
A manual reset is possible.
E
B
A
B
Manual
Error when restoring the system state: 
Checksum erroneous.
The thermal memory of the bimetal function is set 
to the max. value. 
The error must be manually acknowledged in 
automatic mode.
E
B
B
B
Manual
Symmetry: The two motor currents deviate from 
each other by more than 33 %.
E
B
A
A
Manual
Phase failure: Phase failure with pending control 
signal
B
B
A
E
Automatic 
2)
Blocking: The max. measurable motor current is 
exceeded for more than 2 s.
E
B
A
B
Manual