INSTALLATION INSTRUCTIONS
FOR "LS" LIMIT SWITCHES
PK 81028
"Plug-in 200LS" Type
Plug switch into an 18PA1 terminal block, tighten
two screws and mounting is complete. Installation
of 18PA1 terminal block (purchased separately) is
covered in instructions which are packed with the
block.
Compact "LS" Type
Two simple methods of mounting: (a) use four 
10
screws from the front, or (b) use four ¼-20 UNC
screws from the back. Make sure conduit connection
is sealed. Locate switch so condensate or oil won’t
drain into switch through conduit.
For "7LS" cavity mount type use four # 10 screws
to fasten the switch plate to the surface. A rubber
gasket seals the plate to the mounting surface.
Use copper, 60/75 degree C wire only.
Terminal screw torque-20 inch pounds max.
COMPACT LS WITHOUT ACTUATOR
ADJUSTING INSTRUCTIONS
Actuator Head
Positioning Lever
To give flexibility in
application, the actu-
ator head may be posi-
tioned in any of four
directions.
(See                   
NOTICE
in "Direction of Actuation".)
Reversing the Roller
The lever assembly is ad-
justable to any position
through 360° by loosening
the socket head screws.
5/32 
inch hexagon key
wrench is required (avail-
able in "Handy Adjusting
Tool Set" 15PA53).
The roller arm may be reversed to face the roller
inside or outside of the arm.