Technical specifications 
 
A.7 Specifications for the analog I/O 
 
Easy Book 
316
 
Manual, 03/2014, A5E02486774-AF 
System 
Voltage Output Range 
Decimal 
Hexadecimal 
± 10 V 
-1 
FFFF 
-361.7 μ V 
-20736 
AF00 
-7.5 V 
-27648 
9400 
-10 V 
-27649 
93FF 
 
Undershoot range 
-32512 
8100 
-11.76 V 
-32513 
80FF 
See note 1 
Underflow 
-32768 
8000 
See note 1 
 
  In an overflow or underflow condition, analog outputs will take on the substitute value of the STOP mode.  
 
Table A- 45  Analog output representation for current (SB and SM) 
System 
Current output range 
Decimal 
Hexadecimal  0 mA to 20 mA 
4 mA to 20 mA 
 
32767 
7FFF 
See note 1 
See note 1 
Overflow  
32512 
7F00 
See note 1 
See note 1 
32511 
7EFF 
23.52 mA 
22.81 mA 
Overshoot range 
27649 
6C01 
 
 
27648 
6C00 
20 mA 
20 mA 
Rated range 
20736 
5100 
15 mA 
16 mA 
723.4 nA 
4 mA + 578.7 nA 
0 mA 
4mA 
-1 
FFFF 
 
4 mA to 578.7 nA  Undershoot range 
-6912 
E500 
 
0 mA 
-6913 
E4FF 
 
 
Not possible. Output value limited to 0 mA. 
-32512 
8100 
 
 
-32513 
80FF 
See note 1 
See note 1 
Underflow 
-32768 
8000 
See note 1 
See note 1 
 
  In an overflow or underflow condition, analog outputs will take on the substitute value of the STOP mode.