Инструкции Пользователя для Bunn JDF-2 S, JDF-4 S, Lighted DisplayCanada
18
Circuit Board LED Indicators - JDF-2S (Early Models)
LED #
LED Color
Illuminates:
1
Green
When the compressor should be ON.
2 Cabinet
Red
When the cabinet temperature is above 50 degrees F.
Flashes slowly when cabinet temperature exceeds 50 degrees F for 4
hours. Dispense functions are locked out under this condition. Power
down the dispenser to reset.
hours. Dispense functions are locked out under this condition. Power
down the dispenser to reset.
Flashes rapidly if dispense is attempted in lockout condition.
Open cabinet thermistor circuit will flash #2 and #3 LED’s 1 time every 3
seconds.
seconds.
Shorted cabinet thermistor will turn #2 and #3 LED’s on steady.
3 Cabinet
Green
When cabinet temperature is below 50 degrees F.
4 Bath
Red
When bath temperature is above 34 degrees F.
Flashes slowly when compressor is in a 6 minute delay period.
Open bath thermistor circuit will flash #4 and #5 LED’s 1 time every 3
seconds. The compressor will not run under this condition.
seconds. The compressor will not run under this condition.
Shorted bath thermistor circuit will flash #4 and #5 LED’s 2 times every 3
seconds. The compressor will not run under this condition.
seconds. The compressor will not run under this condition.
5 Bath
Green
When bath temperature is below 34 degrees F.
FUNCTION LIST
P3585
FIG 18 JDF-2S
(Early Models)
1
3
5
2
4
44744.2 062912