• Argus Link (Multiple boiler applications only)
• Outdoor Sensor, if used.
A.  Provided with boiler.
B.  Locate outdoor sensor to protect against wind and 
direct sunlight. Mounting instructions provided with 
sensor. 
C.  Maximum wire length is 100 ft (30m) for 22 ga. 
wire, or 150 ft (45m) for 18 ga. wire.
D.  Connect wires to OUTDOOR SENSOR terminals. 
Wires are interchangeable.
• System Sensor (Multiple boiler applications only)
• Domestic Hot Water (DHW) Thermostat, if used.
A.  Use temperature control with dry contacts rated 
at 0.5 amps @ 120 VAC. Boiler control does not 
provide power to DHW temperature control. 
NOTICE
IMPORTANT: Do not apply power to DHW T-T 
terminals.  Dry contact only, use of isolation relay 
may be necessary.
B.  Maximum wire length is 330 ft (100m) 22 gauge wire.
C.  Connect wires (interchangeable) to DHW T-T 
terminals. Wires are interchangeable.
• Central Heating Thermostat
A.  Use thermostat or boiler system control with dry 
contacts related 0.5 amps @ 120 VAC.
 
Boiler control 
does not provide 24 VAC power to central heating 
thermostat.
B.  Locate and install thermostat per manufacturer's 
instructions. Maximum wire length is
 
330 ft (100m) for 
22 ga. wire.
C.  Connect wires to CH T-T terminals. Wires are 
interchangeable.
• Low Water Cutoff (LWCO)
Connect LWCO switch leads to terminals provided. See 
Figures 14.1 thru 14.4 for wiring diagrams. Provide 
power to LWCO per manufacturer's instructions. 
NOTICE
Boiler transformer does not have adequate VA to 
power accessories, including LWCO.
FIGURE 
8-4 
External Connections  (Do not apply external voltage to external terminals.)
NOTICE
Use dry contact for wires to CH T-T terminal and  
DHW T-T terminal. E33 error code is displayed if 
voltage is sent back to the control board. If error 
is not corrected for extended period of time, this 
voltage can permanently damage control board.
8 - ELECTRICAL CONNECTIONS
FIGURE 
8-3 
 Isolation Relays for CH System Pump 
and DHW Pump
DHW     
Pump
CH      
Pump 
Relay 
120VAC 
coil
DHW      
Pump 
Relay 
120VAC 
coil
CH      
Pump