DRAFT INDUCER TEMPERATURE SAFETY 
SWITCH
Draft inducer runs through 30 second post purge and 
switches OFF.
Circulator runs with thermostat on call for heat.
When temperature safety switch contacts connect 
before end of call for heat, control goes in normal 
light-off sequence.
LOSS OF COMBUSTION AIRFLOW
If combustion airflow is lost while burner is firing 
(Differential air pressure switch contacts open) gas 
valve is de-energized. 
Valve and flame lights go out.
Draft inducer runs through 30 second post purge.
If call for heat remains, IBC waits 5 minutes for airflow 
to be re-established.
If airflow does not re-establish control lockout problem 
with combustion airflow. 
Purge light blinks
Control automatically reset after 15 minutes.
LOSS OF FLAME SIGNAL
If established flame signal is lost while control expects 
burner is operating, control immediately de-energizes 
gas valve. 
Valve and flame lights go out.
Draft inducer runs through 30 second post purge.
Control attempts to light boiler 3 times. If flame is not 
proven, control lockout problem establishing flame 
signal. 
Valve light is blinking
Control automatically resets after 1 hour.
HIGH  LIMIT  CONTROL                                    
[REFER TO PAGE 37 FOR MORE INFO]
If boiler water temperature reaches high 
limit setpoint, high limit n.c. contacts open 
immediately, closing gas valve. 
Valve and flame lights go out.
Draft inducer continues to run for 30 second post 
purge and switch OFF.
Circulator runs as long as thermostat calls for 
heat.
When high limit contacts connect before end of 
call for heat - control goes into normal light-off 
sequence.
CASTING TEMPERATURE SAFETY SWITCH
If burner operates when boiler has no water, 
aluminum boiler sections heat up rapidly.
Casting temperature safety switch contacts will 
open, breaking 24 volt power to IBC. 
Power indicator light goes out. 
Requires manual reset to re-close contacts.
 
Power light goes out.
CIRCULATOR PUMP
Circulator is energized as long as thermostat calls 
for heat during lockout.
Recovery from any lockout requires reset, which 
can be accomplished by:
(a) Removing and re-establishing thermostat’s        
 call for heat or turning service switch off   
 
and back on; 
or 
(b) Waiting for control to automatically reset after 
15 minutes for loss of combustion airflow or one 
hour for loss of flame.
12 - DETAILED SEQUENCE OF OPERATION
If draft inducer temperature reaches temperature 
safety switch set-point, safety switch contacts open 
immediately, closing gas valve 
(light goes out)
.