Periodic maintenance  66 
Component to be inspected 
Task 
Frequency 
Capable Party 
— 
Compare the following with site 
indications (if available): 
 
CWS/CWR temperature 
 
CWS/CWR pressure 
 
Flow rate (if possible) 
(Investigate discrepancies, trouble 
shoot, and replace as necessary.) 
Annually  
Qualified personnel 
— 
POD SHUT DOWN REQUIRED 
Calibrate (zero out) POD 
differential pressure sensors. 
(Investigate discrepancies, trouble 
shoot, and replace as necessary.) 
Annually 
Qualified personnel 
Lighting 
Visual inspection of lighting 
fixtures and lamps. Replace 
components upon failure. 
As needed or 
Quarterly 
Licensed electrician/ 
Qualified personnel 
 
 
Fire alarm and suppression system 
 
Component to be inspected 
Task 
Frequency 
Capable Party 
Full system functional check 
Inspect and perform a functional 
check of the system. 
As required by 
local code 
Authorized technician 
Fire panel 
Inspect and test fire panel 
battery backup system. 
Bi-annually 
Authorized technician 
VESDA 
Inspect and test VESDA power 
supply. 
Quarterly 
Authorized technician 
— 
Inspect the VESDA pipe 
network. 
Bi-annually 
Authorized technician 
— 
Inspect the VESDA filter. 
Replace as necessary. 
Annually 
Authorized technician 
— 
Conduct a VESDA pipe integrity 
smoke test. 
Annually 
Authorized technician 
— 
Check the VESDA pipe flow. 
Annually 
Authorized technician 
— 
Clean the VESDA sampling 
points. 
Every 2 years 
Authorized technician 
— 
Flush the VESDA pipe network.  Every 2 years 
Authorized technician 
— 
VESDA system air 
sampling/smoke test 
As required by 
local code 
Authorized technician 
Suppression system 
Suppression system test 
As required by 
local code 
Authorized technician 
— 
Fire-pull visual and operational 
inspection 
As required by 
local code 
Authorized technician 
— 
Fire strobe and horn visual and 
operational inspection 
As required by 
local code 
Authorized technician 
 
 
HP POD 20c structure 
 
Component to be inspected 
Task 
Frequency 
Capable Party 
Complete structure 
Visually inspect the structural 
integrity. 
Annually 
Qualified personnel