Краткое Руководство По Установке для HP Performance Optimized Data Center (POD) 40c

Скачать
Страница из 41
 
HP POD 40c G2 capacities  7 
HP POD 40c G2 capacities 
HP POD 40c G2 capacity limitations 
The capacity limitations for the HP POD 40c G2 are separated into two categories: electrical power and 
mechanical cooling capacities. Both of these categories are interdependent and must be considered in 
conjunction with the overall customer requirements. 
 
Electrical power capacities (critical IT power) 
The electrical system of the HP POD 40c G2 has two main feeds, A and B, each rated at 800 A 415 VAC 
Wye 3-Phase. 
 
Mechanical cooling capacities 
The HP POD 40c G2 cooling system consists of 6 zones. Each zone includes 2 heat exchangers and 18 fans. 
Cooling capacities are based on: 
 
Chilled water inlet temperature of 15.6ºC (60ºF) 
 
Heat exchanger fluid delta temperature of 5.5ºC (10ºF) 
 
Pure water cooling 
 
Chilled water flow rate of 908 lpm (240 gpm) 
 
Average air flow of 2000 cfm per rack 
 
Overall system capacities 
The HP POD 40c G2 overall system capacities are provided in the following table. It is the customer's 
responsibility to understand the level of redundancy required for their particular application and its 
associated limiting factor. 
   
Redundancy level 
Electrical (kW)   
Thermal (kW) 
Limiting factor 
— 
600 
Thermal* 
N+1 
— 
400 
Thermal* 
2N 
576 
300 
Thermal* 
 
*The thermal limitation factors are described in "Mechanical cooling capacities (on page 
)."