Overview  5 
Overview 
About this document 
This document outlines the site and preparation requirements for a 6 m (20 ft) HP POD 20c as it is being 
released in North America. The customer must provide a qualified architectural or consulting engineering 
team to generate site-specific documents for each HP POD 20c installation, including final site drawings. The 
customer site installation design must comply with all national, regional, and local regulations, ordinances, 
codes, and the specifications that are listed in this document. 
This guide is part of the core documentation for the HP POD 20c. The actual location of various components 
or included subsystems and their operation for your site-specific HP POD 20c might vary from what is 
described in this document. For information that is specific to your HP POD 20c, see the drawings included 
in the Operations and Maintenance Manual for the HP Performance Optimized Datacenter 20c, or contact 
HP. 
 
Safety and NEC compliance 
The HP POD 20c is certified to UL 69050-1/IEC 60950-22 as an Information Technology Product and 
classified according to the National Electric Code NFPA 70. For more information, see "HP POD 20c 
regulatory compliance (on page 
)." 
The HP POD 20c is not suitable for long-term human occupancy. The HP POD 20c is Listed as a Product that 
provides service access areas for periodic maintenance and service. These areas must be used only by 
owner-authorized and qualified personnel who are trained in the maintenance and service of the HP POD 
20c components. 
  
 
IMPORTANT:
  Before installing the HP POD 20c, consult your local AHJ for applicable 
regulations and to review site-specific location guidelines. If needed, obtain any necessary 
permits. 
  
Additional considerations for safety and NEC compliance are as follows: 
 
The HP POD 20c is listed as an Information Technology Product to UL 60950. 
 
The HP POD 20c is evaluated as a "non-inhabitable product" that provides "service access" areas for 
customer-authorized, qualified, and trained service personnel. 
 
The electrical connections of the HP POD 20c are evaluated as feeder connections for connection to an 
existing facility, and are not suitable as "service entrance" for connection to the utility. 
 
The HP POD 20c is designed for stationary installation outdoors in a Pollution Degree 3 environment, 
in restricted access locations, with field wiring terminals provided for permanent supply connections. 
 
The HP POD 20c meets the following ratings. 
 
Feature 
Specification 
Category 
Rated Overvoltage Category III 
Protection 
Surge protection device