Removal and replacement procedures  33 
2. 
Secure the thermister with tie wraps (2). 
 
 
External chilled water flow actuator 
The external chilled water flow actuator is located on top of the HP POD 40c G2. 
 
You need a wrench for installation. 
 
Removing the external chilled water flow actuator 
1. 
Open and danger tag the associated circuit breaker in the ECS cabinet. The circuit breakers are 
identified on the panel schedule.