Site requirements  14 
Parameter 
Range 
Calcium hardness (CaCO
3
0–200 ppm 
Magnesium hardness (CaCO
3
0–150 ppm 
Copper (Cu) 
< 0.20 ppm 
Iron (Fe) 
< 3.0 ppm 
Aluminum (Al) 
< 0.50 ppm 
Sodium (Na) 
0–1000 ppm 
Silica (SiO
2
0–150 ppm 
Zinc (Zn) 
< 1.0 ppm 
Manganese (Mn) 
< 0.1 ppm 
Phosphate Ortho- (PO
4
)  
< 3 ppm 
Bacteria 
< 1000 CFU/ml 
Suspended solids 
< 10 ppm 
 
If your water is out of range, consult a water quality expert. 
The following table describes the chilled water system specifications for the HP POD 20c. 
 
Feature 
Specification 
Facility input temperature to the HP POD 
20c 
12º to 24ºC (55º to 75ºF) 
Max design pressure 
1,034 kPa (150 psi) 
HP POD 20c pressure drop 
172.4 kPa (25 psi) 
HP POD 20c water flow rate 
454 lpm (120 gpm*) 
Chilled water supply and return 
connections 
Two DIN PN16 DN80 flanges 
 
 
Piping materials 
Do not use the following interconnecting piping materials in a closed water system: 
• 
Oxidizing biocides 
• 
Aluminum components 
• 
Brass components with high levels of zinc 
• 
Non-stainless steel iron components 
• 
PVC 
   
 
IMPORTANT:
  Even though some PVC grade piping materials are designed to handle the 
expected water pressure, the use of PVC materials should be reviewed and approved by the 
customer site engineers. 
   
 
Power infrastructure installation 
When determining the final location of the power connections, consider the following: 
• 
Distance between the facility utilities and the location of the HP POD 20c