Site requirements 14
Parameter
Range
Calcium hardness (CaCO
3
)
0–200 ppm
Magnesium hardness (CaCO
3
)
0–150 ppm
Copper (Cu)
< 0.20 ppm
Iron (Fe)
< 3.0 ppm
Aluminum (Al)
< 0.50 ppm
Sodium (Na)
0–1000 ppm
Silica (SiO
2
)
0–150 ppm
Zinc (Zn)
< 1.0 ppm
Manganese (Mn)
< 0.1 ppm
Phosphate Ortho- (PO
4
)
< 3 ppm
Bacteria
< 1000 CFU/ml
Suspended solids
< 10 ppm
If your water is out of range, consult a water quality expert.
The following table describes the chilled water system specifications for the HP POD 20c.
The following table describes the chilled water system specifications for the HP POD 20c.
Feature
Specification
Facility input temperature to the HP POD
20c
12º to 24ºC (55º to 75ºF)
Max design pressure
1,034 kPa (150 psi)
HP POD 20c pressure drop
172.4 kPa (25 psi)
HP POD 20c water flow rate
454 lpm (120 gpm*)
Chilled water supply and return
connections
Two DIN PN16 DN80 flanges
Piping materials
Do not use the following interconnecting piping materials in a closed water system:
•
Oxidizing biocides
•
Aluminum components
•
Brass components with high levels of zinc
•
Non-stainless steel iron components
•
PVC
IMPORTANT:
Even though some PVC grade piping materials are designed to handle the
expected water pressure, the use of PVC materials should be reviewed and approved by the
customer site engineers.
customer site engineers.
Power infrastructure installation
When determining the final location of the power connections, consider the following:
•
Distance between the facility utilities and the location of the HP POD 20c