4.12.5
Externally Adjusted Registers
The FX
1S
 and FX
1N
 have built in “setting
po ts ”   w h i c h   a r e   us e d  t o  a d j us t   t he
c o n t e n ts   o f   c e r ta i n   d e d i c a t e d   d a ta
registers. The contents of these registers
can range from 0 to 255. This is a built in
feature and requires no additional setup
or programming.
The FX
2N
 and FX
2NC
 do not have this
feature, however, an additional special
function unit is available which provides
the same function. The unitrequired  is
the FX
2 N
-8AV-BD. For use, this unit
requires the applied instructions VRRD
function 85 (Volume Read) and VRSC function 86 (Volume Scale). 
Uses:
This facility is often used to vary timer settings, but it can be used in any application 
where a data register is normally found, i.e. setting counters, supplying raw data, even 
selection operations could be carried out using this option.
FX
1S
 FX
1N
FX
2N
FX
2NC
Number of
setting pots
2 points,
 plus 8 points: Supplied by using 
the additional special function 
board
FX
2N
-8AV-BD
8 points: Supplied by using the 
additional special function board
FX
2N
-8AV-BD
Number of 
controlled
data registers
   1: D8030
   2: D8031
Additional 8 points selected by 
the user when applied 
instructions VRRD and VRSC 
are used.
Selected by the user when 
applied instructions VRRD and 
VRSC are used.
RUN
STOP
Setting pot
of an FX
1S