The 
36J27 combination gas valve is designed for 
direct spark ignition (DSI) and hot surface ignition 
(HSI) system applications. This control is equipped 
with redundant and main solenoid valves that control 
gas flow to the main burners, a pressure regulator 
and  a  two-position  on/off  switch  for  regulation 
and electrical shut-off of the solenoid valves. Upon 
signal from an integrated furnace control, the valve 
modulates outlet pressure.
Fig. 
1 – 36J27 Modulating Gas Valve 
CONTROL LABEL
36J27-554
DSI and HSI Modulating Combination Gas Valve
INSTALLATION INSTRUCTIONS
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY 
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE 
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
 
 
DESCRIPTION
 
 
SPECIFICATIONS
www.white-rodgers.com
www.emersonclimate.com
PART NO. 
37-7004D
Replaces 37-7004C
1345
Pressure Regulator Adjustment Range ( inches W.C.)
Pipe Sizes
CSA Std. Gas
.64 Sp. Gr. 
(
1000 BTU/CU. FT.)
LP Gas
1.53 Sp. Gr.
(
2500 BTU/CU. FT.)
Adjustment
Range
(NAT., IN. W.C.)
Adjustment
Range
(LP., IN. W.C.)
1/2” x 1/2” NPT 
20,000 – 210,000
BTU/HR
32,600 – 340,000
BTU/HR
0.40 – 4.0
1.3 – 11.5
For L.P. Gas Use Conversion Kit 
F92-1021
1.0" Pressure Drop Capacity
Pipe Sizes (NPT)
CSA Std. Gas
.64 Sp. Gr. 
(
1000 BTU/CU. FT.)
LP Gas
1.53 Sp. Gr.
(
2500 BTU/CU. FT.)
1/2” x 1/2” (Vertical or Upright)
140,000 BTU/HR
226,800 BTU/HR
CONTENTS
Description   ................................................  
1
Specifications  .............................................  
1
Mounting Positions ......................................... 2
Precautions  ................................................  
3
Installation   .................................................  
4
 
System Wiring
Adjustment  ................................................  
5
 
Pressure Regulator Adjustment
Lighting Instructions....................................
 6
Ambient Temperature ....  
-40° to 175°F
Pressure Rating ..............  
14” W.C. (1⁄2 PSI) max.
Voltage ...........................  
24 VAC
Frequency.......................  
60 Hz
Total Current ..................  
1.0A
Pulse Width Modulation (PWM):
                                                       Low level: 
0 – .03 volts
                                                       High level: 
3 – 5.5 volts
Modulation .....................   
35% – 100% opening
                                                       with 
1% increments
Regulator Vent Outlet ....  accepts 
5/16" I.D. hose
Rotary dip switch for pressure regulation adjustment
Precalibrated for LP – simplifies conversion