 CGi-4E Gas-Fired Water Boiler — Boiler Manual
38
Part Number 550-110-711/1108
Operation — sequence
9a
1. 
Read Operating instructions
 on page 41. This information is 
also located on a label on the inside of the boiler jacket door 
panel.
2. 
Raise 
room thermostat to call for heat.
3. 
Circulator  energizes. 
If limit circuit is closed, the inducer 
starts. After  pressure  switch  proves  proper  airflow,  control 
module initiates 30-second prepurge.
4. 
Control  module  sparks
 the pilot and opens pilot valve in 
main gas valve.
a.  If pilot 
does not 
light within 15 seconds, pilot valve is closed 
and spark generator is turned off. Control module initiates a
15-second postpurge, then starts a new cycle.
b.  If pilot 
does 
light and control module senses flame current, 
spark generator is turned off and main valve opens.
5.  The CGi-4E timer relay delays high fire for the first 60 seconds
of main flame.
6. 
During main burner operation:
a.  Control module monitors pilot flame current.
If signal 
is lost
, main valve closes, spark generator activates and 
sequence returns to step 
4
.
b. 
If power is interrupted
, control system 
shuts off
 pilot 
and main gas valves and restarts at step 
1
 
when power is 
restored.
7.  In the event the 
limit control shuts down the boiler 
— The 
control module closes the pilot and main gas valves, but keeps 
the inducer operating for 15-second postpurge.
 
— The circulator continues to operate.
8. 
Lower 
room thermostat setting to stop call for heat. Ther-
mostat  is  satisfied  —  Pilot  and  main  gas  valves  are  closed 
— Inducer operates for 15-second postpurge — Circulator
is shut off.
9.  Boiler is now in the
off cycle
.
10. 
Repeat 
steps 
1
 
through 
6
 
several times to verify operation.
11. 
Return 
the thermostat to normal setting.
12. Set thermostat heat anticipator setting as instructed in
Figure 
31
, page 40.