Справочник Пользователя для Weil-McLain GOLD CGI-4E

Скачать
Страница из 68
GOLD
 CGi-4E Gas-Fired Water Boiler — Boiler Manual
48
Part Number 550-110-711/1108
Troubleshooting — general
11a
Air pressure switch
 
Make sure boiler water temperature is 
100 °F or cooler before starting proce-
dure to obtain appropriate readings.
 
The boiler will not operate correctly un-
less pressure switch hoses are correctly 
located.  The  red  hose  connects  from 
the right side (negative) hose barb to 
the flue collector. The white hose con-
nects from the left side (positive) hose 
barb of the switch to the connector box 
(between flue collector and inducer) as 
shown in 
Figure 36
, page 49.
Check pressure switch setting
1.  See
Figure 36
page 49, and 
Table 9
.
2.  Remove  both  air  pressure  switch  hoses  from  air  pressure 
switch.
3.  Install  tees  and  tubing  as  shown  in 
Figure  36
,  page  49,  to 
inclined manometer.
4.  Turn off gas valve and set thermostat to call for heat. Inducer 
will run but burners will not ignite.
5.  Check for 24 VAC between both air pressure switch termi-
nals.
Troubleshooting air pressure reading
1.  If manometer reading is lower than the setpoint of the switch 
(see
 Table 9
) — check for possible causes:
•  blockage in hoses
•  obstruction in inducer housing outlet
•  loose inducer wheel on motor shaft
•  inducer motor not in proper rpm
•  inducer back plate not sealed properly
•  blockage in block assembly
•  blockage in flue pipe or termination
•  incorrect pressure switch
6.  If manometer reading is above the setpoint of the switch (see 
Table 9
), but there is not 24 VAC between both air pressure
switch terminals — replace air pressure switch.
Return to normal operation
When pressure reading is correct and air pressure switch is oper-
ating properly — remove tees and reinstall hoses to air pressure 
switch.
Table 9 
Pressure switch setpoint (for elevations 
above 2,000 ft, contact your local Weil-
McLain sales office for details.)
Boiler model number
Inches W.C.
CGi-4E
1.36
 
Label  all  wires  prior  to  disconnection  when 
servicing  controls.  Wiring  errors  can  cause 
improper and dangerous operation.
Never jumper (bypass) rollout thermal fuse ele-
ment or any other device except for momentary 
testing as outlined in 
Troubleshooting Charts
Severe  personal  injury,  death  or  substantial
property damage can result.
Before troubleshooting:
1.  Have the following items:
a.  Voltmeter that can check 120 VAC and 24 VAC.
b.  Microammeter with a minimum scale range of 0-25.
c.  Continuity checker.
d.  U-tube manometer.
2.  Check for 120 VAC (minimum 102 VAC to maximum 132 VAC) to 
boiler.
3.  Make sure thermostat is calling for heat and contacts (including appro-
priate zone controls) are closed. Check for 24 VAC between thermostat 
wire nuts and ground.
Check the following:
1.  Wire connectors to control module are securely plugged in at module 
and originating control.
2.  Air pressure switch hoses are properly and securely plugged in and are 
not damaged.
3.   Verify gas supply pressure:
a.  With boiler OFF — 13” w.c. maximum natural or propane gas 
pressure upstream of gas valve.
b.  With boiler ON — Upstream: 5” w.c. minimum natural gas pres-
sure or 11” w.c. propane gas pressure upstream of gas valve.
4.   Verify gas manifold pressure (downstream of gas valve):
a.  Natural gas: 
Manifold pressure, high fire: 3.50” w.c.
 
Manifold pressure, low fire: 0.90” w.c. while in low fire at start-up 
(60 seconds)
b.  Propane gas: 
Manifold pressure, high fire: 10.0” w.c.
 
Manifold pressure, low fire: 3.50” w.c. while in low fire at start-up 
(60 seconds)
c.  If necessary, adjust gas pressure on the gas valve as shown below. 
After adjustments, refer to page 35 to check the flame.
High-fire gas pressure adjustment
Low-fire gas pressure adjustment
Honeywell VR8204Q two-stage gas valve