Инструкции По Установке для White Rodgers 21V51U-843 Universal Two-stage HSI Integrated Furnace Control Kit

Скачать
Страница из 8
3
The 50V51-843 has only one serviceable part –an automotive 
type fuse, which protects the low voltage transformer from dam-
age if the output is short-circuited. If the fuse has opened up, 
remove whatever caused the short circuit and replace the fuse 
with only a 3 Amp automotive type fuse. If the fuse does not 
correct the condition, replace the entire 50V51 control. There 
are not other user serviceable parts.
Following installation or replacement, follow appliance manu-
facturer’s recommended installation or service instructions to 
insure proper operation.
INSTALLER MUST READ FOR PROPER 
INSTALLATION
  Wiring harnesses are included in this package to complete 
the  installation  of  the 
“UNIVERSAL  50V51-843”  for 
Goodman applications. 
  Installer must read 
Option Switch Settings section and set 
switches for proper control operation.
  For replacing the ignitor, a 
UNIVERSAL 21D64-2 is included. 
For proper installation, refer to the instructions included in 
the 21D64-2 kit.
 
IMPORTANT: The installer may have to enlarge existing igni-
tor hole to accommodate 21D64-2 larger (.394”) diameter.
MOUNTING AND WIRING
All wiring should be installed according to local and national 
electrical codes and ordinances.
The control must be secured to an area that will experience a 
minimum of vibration and remain below the maximum ambient 
temperature rating of 175°F. The control is approved for minimum 
ambient temperatures of -40°F.
Any orientation is acceptable.
Refer to the wiring diagram and wiring table when connecting 
the 50V51 control to other components of the system.
UL approved, 105°C rated 18 gauge min., stranded, 2/64” thick 
insulation wire is recommended for all low voltage safety circuit 
connections. Refer to 50V51
 specification sheet for recommended 
terminals to mate with those on the control.
UL approved, 105°C rated 16 gauge min., stranded, 4/64” thick 
insulation wire is recommended for all line voltage connections. 
Refer to 50V51 specification sheet for recommended terminals 
to mate with those on the control.
 GOODMAN NOTE
FOR  GOODMAN  50V51-289  APPLICATION, ThERE  ARE
TWO ADAPTER HARNESSES INCLUDED IN THIS PACKAGE 
TO COMPLETE THE INSTALLATION.
 
 INSTALLATION
 
 OPTION SWITCH SETTINGS
MOTOR OPTIMIZATION
Amana/Goodman/Trane/Lennox/Thermo Pride – The motor 
configuration DIP switches 
S3 and S4 must be set to match set-
tings of the original furnace settings for proper motor function. To 
set the new board for the motor function, the DIP switches must 
be set to match the settings of the board being replace.
IMPORTANT: Be sure to use proper switches for new board 
settings. Switch locations on old board may not be the same 
location as on the new board.
York – The existing board has four shunt jumper banks to set 
motor function configuration. The four jumper banks are des-
ignated 
DELAY (E45)COOL (E43)HEAT (E46)ADJ. (E44)
Each jumper bank has four pair of pins to have jumper installed 
to determine the type of voltage to the motor. These pin pairs 
are 
A (no signal) B (positive Half-wave rectified), C (negative 
Half-wave rectified), 
D (Full-wave unrectified).
DELAY
A
B
C
D
A
B
C
D
A
B
C
D
COOL
Jumper Banks
(Existing Board
Example Settings)
HEAT
ADJ
E45
E43
E46
E44
SW4
SW3
1  2  3  4
ON
OFF
1  2  3  4
ON
OFF
Switch Position 
50V51-843 
(New Board)
SW4
5  6  7  8
ON
OFF
SW3
1  2  3  4
ON
OFF
Existing 50V51 
or 50V61
On the new board, the motor functions must be duplicated on 
DIP switched 
S3 and S4 per the following table.
SW4
SW3
1  2  3  4
ON
OFF
1  2  3  4
ON
OFF
Switch Position 
50V51-843 
(New Board 
Example Settings)
Motor Configuration Settings
A
B
C
D
No Signal Positive 
Half Wave
Negative 
Half Wave
Full 
Wave
Delay
S4-1
OFF
ON
OFF
ON
S4-2
OFF
OFF
ON
ON
Cool
S3-1
OFF
ON
OFF
ON
S3-2
OFF
OFF
ON
ON
Heat
S4-3
OFF
ON
OFF
ON
S4-4
OFF
ON
ON
ON
Adjust
S3-3
OFF
ON
OFF
ON
S3-4
OFF
OFF
ON
ON