Инструкции По Установке для White Rodgers 21V51U-843 Universal Two-stage HSI Integrated Furnace Control Kit

Скачать
Страница из 8
7
 TROUBLESHOOTING
SYSTEM LOCKOUT
When  a  system  lockout  occurs  (1hour),  the  gas  valve  is  de-
energized, the low speed inducer blower is energized for the 
60 second interpurge period and the circulator is energized for 
selected heat off delay if it was previously ON. The diagnostic 
indicator  light  will  flash  the  fault  that  is  present  (refer  to 
diagnostic table).
To  reset  the  control  after  system  lockout,  do  one  of  the
following:
System Reset
Remove 24 VAC power to the control for twenty (20) seconds 
or longer to reset the control.
Thermostat Reset
Remove the call for heat from the thermostat for a period of 
between (1) second and less 20 seconds. If flame is sensed 
with the gas valve de-energized, interrupting the call for heat 
at the thermostat will not reset the control.
Auto Restart
After one (1) hour of internal or external lockout, the control 
will automatically reset itself and go into an auto restart purge 
for 15 seconds.
DIAGNOSTIC FEATURES
The  control  continuously  monitors  its  own  operation  and  the 
operation  of  the  system.  If  a  failure  occurs  the  diagnostic 
indicator LED (DSI) will flash a “RED” failure code. 
If a failure
is internal to the control the “RED” indicator will stay on
continuously.  In  this  case,  the  entire  control  should  be
replaced as the control is not field-repairable.
If the LED 
is  continuously  OFF,  there  may  be  no  power  to  the  control 
or  a  failure  within  the  control.  If  the  sensed  failure  is  in  the 
system  (external  to  the  control),  the  LED  will  flash  RED  in 
the sequence listed in the Diagnostic Table. The LED will also 
indicate  “System  Status”  as  per  the  Amber  and  Green  LED 
signatures listed in the Diagnostic Table. The LED will flash one 
RED flash at power up.
CFM INDICATOR 
The LED (DS2) CFM flashes when the blower motor is running. 
The flashing indicates the motor CFM (cubic feet per minute) 
air flow designated by the furnace manufacturer. Consult the 
furnace manufacturer for flash code detail.
FAULT CODE RETRIEVAL 
To retrieve fault codes, push and release the “LAST ERROR” 
button  for  more  than  1/5  second  and  less  than  5  seconds. 
(Control will indicate this period by solid GREEN for 1/5 secs. 
to  5  secs.). The  LED  will  flash  up  to  five  stored  fault  codes, 
beginning with the most recent. If there are no fault codes in 
memory, the LED will flash two green flashes. The control will
flash the most recent error first and the oldest error last (last in 
first out). There shall be 2 seconds between codes. Solid LED 
error codes will not be displayed.
NOTE
These error codes may be different from furnace label or
furnace manual.
NORMAL OPERATION – hEAT ON
When  the  thermostat  calls  for  heat  the  module  verifies  the 
pressure switches are open and energizes the inducer (high 
speed) and optional humidifier contacts. When the low pressure 
switch contacts close a 15 second pre-purge begins. After 15 
seconds the inducer switches to low speed and the 120 VAC 
ignitor is energized. The ignitor warms up for 17 seconds and 
the gas valve is energized on low fire. Flame must be detected 
within  4  seconds.  If  flame  is  detected,  a  45  second  heat, 
fan  on  time  delay  begins. This  allows  the  heat  exchanger  to 
warm  up  before  energizing  the  circulator  on  low  speed  and 
(optional) Electronic Air Cleaner contact. When the thermostat 
(or module) initiates second stage the inducer is energized at 
high speed.
This  closes  the  second  stage  inducer  pressure  switch  then 
energizes the second stage on the gas valve and then the high 
heat circulator speed.
NORMAL OPERATION – hEAT OFF
When  the  thermostat  satisfies  for  second  stage,  the  control 
will switch high speed inducer and high fire gas valve to low 
speed inducer and low fire gas valve. After the 30 second high 
heat fan delay the circulator will drop to low speed. When the 
thermostat satisfies for first stage the gas valve de-energizes 
and the inducer will run low speed for a 15 second post-purge. 
The circulator runs until the heat off delay ends. 
Note: If the module is configured for a single stage thermostat 
and running on second stage when the call for heat ends, the 
circulator will drop to low speed after 30 seconds and continue 
until the heat off delay ends.
COOL MODE
In  a  typical  system,  a  call  for  cool  is  initiated  by  closing 
and 
G. This energizes the compressor and the electronic air 
cleaner (optional). The electronic air cleaner and the 
and (
or 
Ylo outputs to the Circulator motor will energize after the 5 
second cool on delay period. After the thermostat is satisfied, 
the  compressor  is  de-energized  and  the  control  starts  a  60 
second  cool  circulator  speed  off  delay.  After  60  seconds  the 
circulator is de-energized.
MANUAL FAN ON MODE
If the thermostat fan switch is moved to the “ON” position, the
electronic air cleaner (optional) and the 
circulator output to 
the circulator motor will be energized. When the fan switch is 
returned to the AUTO position, the 
circulator output and the
electronic air cleaner are de-energized.
 