Справочник Пользователя для Westinghouse SE 6000

Скачать
Страница из 180
S
ECTION
 6: S
YSTEM
 A
DMINISTRATION
6-11
Activate CodeExtension.  Required.  System code number for the type of action to be
performed.  The extension applies to camera presets for pan and tilt, or image verification
when used with a Polaroid ID-4000 system.  See table following this field description list.
Deactivate CodeExtension.  Optional.  If this task is to be automatically controlled by a time
coded event, enter the activate / deactivate code to be executed when the event time code
ends.  See table following this field description list.
User Interactive.  Conditional (applies to event times).  A Y/N field to indicate if a timed task
can be cancelled by an operator.
A
CTIVATE
 / D
EACTIVATE
 C
ODES
09
REQ MANUAL ACCESS
Request to perform manual access.
29
FORGIVE PASSBACK
Request to forgive passback.
41
MANUAL UNLOCK
Unlock a sensor / lock for an unlimited time.
45
MANUAL LOCK
Lock a sensor /lock.
46
TIME UNLOCK
Unlock a sensor / lock for the amount of time specified by the
hardware settings, or, where applicable, by the amount of time in
the Unlock Time field of the reader entry screen.
56
BUILDING OPEN
Set building mode to OPEN
57
BUILDING LIMITED
Set building mode to LIMITED
58
BUILDING CLOSED
Set building mode to CLOSED
70
DEACTIVATE OUTPUT
Turn off the specified output.  Use this code if you are elsewhere
turning an output on for an unlimited time.
#
Activate / Deactivate Code Explanation
71
ACTIVATE  OUTPUT
Turn on a specified output for the amount of time shown in the Time
field on the point entry screen.  If Time=0, the output will be on for
an unlimited amount of time, and you must turn it off with an a
deactivate output code.
80
Chain Task
Jumps to another group of task records and is used to consolidate
multiple task into a separate task.
#
Activate/Deactivate Code
Explanation
81
EXTENDED PROCESSING
Instruct extended processing poller to process a transaction.  Use
with elevator, parking control, VIP2, and poller transactions with a
point ID which matches the poller record for these functions.
89
SHUNT POINT
Shunt a specified point.
90
UNSHUNT POINT
Unshunt a specified point.
91
REQUEST RESET DEVICE Perform a device reset for an applicable device.
92
REQUEST RESET KEYS
Perform a key download for an applicable device.