4-21
Tenant.    Optional  (zoom  available).    Enter  a  four-digit  maximum  tenant  code  number.
Default is 0.

Computer ID.  Required.  Enter the ID of the computer on which this poller is to run.  Default
is 0—host computer.
 
Poller Number.  Required.  Enter the number of the corresponding poller-parameter file.
Refer to the configuration sheet detailing the factory-assigned poller numbers.
5
Poller Type.  Required.  Use the zoom feature (F7) to access the Poller Type Display screen.
Once there, arrow down to the required poller type, press F1, and the poller type number is
entered automatically into the Poller Entry screen.
6
Disable.  Not currently implemented.
7
Zone Number.  Required.  Enter a four-digit maximum zone number.  Default is 0.
D
EVICES
The most common devices used with SE 6000 system are the WSE NexSentry, 708P, 8xx-
series and 422 ACUs.  Other devices supported include:
Opto 22 input / output controllers
CCTV switchers
Radionics alarm panels
One or more additional SE 6000 systems used as local controllers
With the exception of the NexSentry, 8xx-series and 422 ACUs, each individual device type
requires its own poller and associated hardware port assignment.
S
IMPLE
 / I
NTELLIGENT
 D
EVICE
 T
YPES
The  terms  simple  and  intelligent  are  often  used  to  describe  certain  device  types  used  in
conjunction with the SE 6000.
Simple  Devices.    With  simple  devices,  the  SE  6000  makes  the  access  decisions  and  also
instructs the device to take various actions.  The 708P ACU is a simple device, for example.
Intelligent Devices.  Depending on system configuration requirements, intelligent devices can
be programmed to make their own decisions concerning access and actions to be taken.  The
devices typically have their own application software and / or firmware, and they maintain their own
internal data files which are used for decision making.  The NexSentry, 8xx-series, and 422 ACUs