12. DUCTS AND REGISTER MEASUREMENTS  
 
(sample calculations)
 
SIMPLIFIED METHOD 
DISTRIBUTION SYSTEM
 
 
Ducts size (heat) 
    4 inch outlet  reduce by 1” 
    5 inch outlet  reduce by 2”     Always by 8” thick 
    6 inch outlet  reduce by 3” 
N.B.: The main duct must be reduced every 2 
outlets. 
 
 
Ducts specifications (heat) 
    Dimensions  Length  Elbow        Average equivalence
 
4” 
10’ 
1 x 90
o
   
Max 4,000 Btu 
 
5” 
10’ 
1 x 90
o  
Max 6,000 Btu 
 
6” 
10’ 
1 x 90
o  
Max 7,000 Btu 
 
 
DAMPER
 
 
For a 4” warm air outlet: 2” x 10” damper 
For a 5” warm air outlet: 2” x 12” damper or 4” x 10” 
For a 6” warm air outlet: 2” x 14” damper or 4” x 12”
 
WARM AIR SYSTEM INSTALLATION
 
 
HOUSE DIMENSIONS 
Example: 28 x 40 bungalow: 1,120 sq. ft. 
 
28 x 40 x 8: 8,960 cu. ft. x 1.8 Ch. air/hr: 
16,128 Btu 
 
Exposed walls:
 
 
40 + 40 + 28 + 28: 136 x 8: 1,088 cu. ft. x 22:  23,936 Btu 
 
Number of windows:
 
 
12 of 3 x 4: 144 x 60:   
 
 
 8,640 Btu 
 
Number of doors:
 
 
2 x 3 x 7: 42 x 100: 
 
 
 
 4,200 Btu 
 
 
 
 
 
 
52,904 Btu 
 
Non-insulated basement:
  25% 
Insulated basement:
  15% 
 
 
 7,906 Btu 
or 54 Btu per sq. ft.
 
 
 
 
60,840 Btu 
FOR ELECTRIC ELEMENTS 80%:48,672 Btu  or   14,28 kW 
TO BE ADDED: House 1 1/2  floor = 25% 
 
 
House 2 floors      = 40% 
 
 
BEDROOM (for example: 12 x 12) 
12 x 12 x 8: 1,152 cu. ft. x 1.8 Ch. air/hr: 
 2,074 Btu 
Exposed walls:
 
12 + 12 x 8: 192 x 22:   
 
 
 4,224 Btu 
Windows:
 
3 x 4 x 60 
 
 
 
             720 Btu 
 
 
 
 
 
             7,018 Btu