Справочник Пользователя для Studer Innotec SI SERIES

Скачать
Страница из 10
STUDER INNOTEC                                                                                                                            SI 
User manual 
SI V3.0 E 
 10 
Technical data 
Model SI 
 
612 
624 
648 
812 
824 
1212 
1224 
1248 
1624 
 
2324 
2348 
 
3324
 
3548 
 
Input voltage (Unom) [V] 
12/24/48
12/24 12/24/48
24 
24V/48  24 
48 
Nominal power  [W] 
600 
800 
1200 
1600 
2300 
3300 
3500 
« Standby » current [mA] 
Power « ON » no load [W] 
25/21/10
2.6 
25/21  
2.8 
25/21/12
4.8 
21 
5.8 
25/17 
25 
13 
30 
17 
Power « ON » no load [W] 
TWINPOWER system 
-------- -------  < 
0.5  < 
0.5 
< 0.6 
< 0.7 
< 0.8 
Maximum efficiency [%] 
91 
92 
93 - 95 
93 - 95  
95 
95 
95 
Length L x 124 (H) x 215 (W) [mm] 
276 
276 
391 
391 
591 
636 
791 
Weight [kg] 
6.9 
10.4 
13.2 
15.2 
27 
30 
38 
 
Input voltage  
Min. - Max.: 
< Unom x 0.95 to Unom x 1.33 
Dynamic correction of Umin. 
- 10% at Pnom 
Output voltage 
True sine 230 Vac 
±3%  
Distortion 
< 2% (at Pnom) 
Dynamic behaviour 
From 0% to 100% load change. Normalization: 0.5 ms   
Frequency  
50 Hz 
±0.01% (Crystal control) 
Charge detection (standby) 
Adjustable: 0.3 
→ 20 W 
Maximum power 15 min 
1.3 – 1.6 x Pnom  / 25°C 
Maximum power 3 min 
1.6 – 2 x Pnom  / 25°C 
Peak power 5s  
3.5 x Pnom 
Asymmetric load 
Up to 2 x Pnom 
Cos 
ϕ  
0.1 – 1 
Protections Overload/Overheat/Short-circuit/Reverse polarity by internal fuse  
IP protection index 
IP 20 complies with DIN 40050/IP 23 with top cover 
Forced ventilation 
From 45°C 
± 3°C 
Overheating protection  
75°C 
± 3°C 
Required battery capacity 
> 5x Pnom/Unom  (recommended value) 
Acoustic level 
Without ventilation: 
< 10 dB              With ventilation:< 35 dB 
EEC conformity 
EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2,       
Dir. 89/336/EEC, LVD 73/23/EEC 
  
 
 
 
 
 
 
 
Other specifications on request (Ex: 115V/60Hz). 
These data are for information only and may change without notice. 
 
 
 
Options 
 
3-phased system (per unit) from SI 1200 
SIxxxxPE 
TwinPower system from SI 1200 
SIxxxxTP 
Top cover IP 23 
C-IP23 
Potential free alarm contact (60V/0.5A) for all models 
SIxxxxA 
Solar charge controller 16A/12-24V for SI 600 and SI 800 
SIxxxS 
Industrial casing in 19’’ rack – 3U x 400 mm from SI 1200 
SIxxxxIND 
 
SI in industrial casing 19’’ rack