96047 First 
Edition
4-7
  
Fault Isolation
Troubleshooting the UPS 
 describes some possible problems and solutions when 
troubleshooting the UPS: 
Table 4-1. Troubleshooting the APC Uninterruptible Power Supply 
Problem and Possible Cause
Solution 
UPS will not turn on. 
ON button not pushed.
Press the ON button once to power on the UPS 
and other equipment. 
UPS not connected to AC power 
supply. 
Make sure the power cable from the UPS to the 
customer’s input power is securely connected at 
both ends. 
UPS input circuit breaker tripped. 
Reduce the load on the UPS by unplugging 
equipment and reset the circuit breaker (on back 
of the UPS) until you isolate the device causing the 
problem (or the UPS). 
Very low or no utility voltage. 
Check the AC power supply to the UPS with a 
table lamp. If the light is very dim, check the input 
voltage. 
Battery not connected properly. 
Check the battery connections. 
UPS will not turn off. 
Internal UPS fault.
Do not attempt to use the UPS. Unplug the UPS 
and contact StorageTek’s Customer Support 
Services* immediately to obtain a new UPS.
UPS operates on battery although normal line voltage exists. 
UPS’s input circuit breaker tripped. 
Reduce the load on the UPS by unplugging 
equipment and reset the circuit breaker (on back 
of the UPS) until you isolate the device causing the 
problem (or the UPS). 
Very high, low, or distorted line 
voltage. 
Move the UPS to a different outlet on a 
different circuit. 
Test the input voltage with the Utility Voltage 
display. If acceptable to the load, reduce the 
UPS’s sensitivity (refer to the APC User’s 
Manual for more information). 
UPS beeps occasionally. 
Normal UPS operation. 
None. The UPS is protecting the load.