Batch automation
SIMATIC BATCH
SIMATIC BATCH hardware
6/3
Siemens ST PCS 7 · November 2007
6
Design
The modularity and flexibility of SIMATIC BATCH are optimally 
supported by the hardware available. The basic hardware from 
the Section "SIMATIC PCS 7 Industrial Workstation" in the Chap-
ter "System-neutral components" can be used for SIMATIC 
BATCH. Please note that the operating system and the ES/OS 
software of the SIMATIC PCS 7 process control system are pre-
installed as standard on the single station, server or client as the 
basic device. If these basic devices are used for SIMATIC 
BATCH, it is possible to extend or reject the existing SIMATIC 
PCS 7 installation, and restore it for the operating system using 
the restore DVD.
Hardware for small plants
For small plants, SIMATIC BATCH can be installed together with 
the OS software on a single station system. You can find further 
details on the hardware for this OS/BATCH single station with the 
ordering data of this section:
• In the Section "SIMATIC PCS 7 Industrial Workstation" of the 
Chapter "System-neutral components"
• In the Section "OS hardware" in the Chapter "Operator system"
A further alternative for small plants is operation of SIMATIC 
BATCH on the starter system SIMATIC PCS 7 BOX 416.
Client/server configuration
Batch process automation typically has a distributed cli-
ent/server configuration with one batch server and several batch 
clients, which together process a plant project. The batch server 
of such a configuration can also be configured with redundancy 
in order to increase availability. 
SIMATIC BATCH clients and OS clients can run on separate or 
common basic hardware. The batch server software is usually 
executed on separate server hardware (Batch Server). Depend-
ing on the load on the operator system, the OS and batch server 
software can also be executed on common server hardware 
(OS/Batch Server).
Since the batch server is only a node on the OS-LAN, we recom-
mend that only the server version of the SIMATIC PCS 7 Indus-
trial Workstation with BCE communication is used. The 
10/100/1000 Mbit/s Ethernet RJ45 port is already onboard and 
can be used for connecting to the OS LAN.
Redundancy
The batch server redundancy is supported by the SIMATIC 
BATCH basic package. The two batch servers of a redundant 
pair of servers have identical configurations. Contrary to the 
case of OS redundancy, they must always be connected via a 
separate Ethernet connection in order to optimize the internal 
communication. Since the batch server is not usually connected 
to the plant bus, the Ethernet network card of the SIMATIC PCS 7 
Industrial Workstation which is provided as standard for the plant 
bus connection can be used for the redundant communication. 
An optical or electrical connection can be used depending on 
the environmental conditions and the distance between the two 
batch servers, e.g. up to 100 m per crossover network cable 
(RJ45 connectors). For details, refer to Manual "SIMATIC PCS 7 
V7.0 fault-tolerant process control systems"; for appropriate ca-
ble material and further accessories, refer to Catalog IK PI.
If the SIMATIC BATCH software and the SIMATIC PCS 7 
OS software are installed together on a redundant pair of serv-
ers, the two servers must be connected together via an addi-
tional desktop adapter network card for the redundant commu-
nication. The serial RS 232 connection described in the Section 
"OS redundancy" is omitted.
For information and components for connection to a redundant 
terminal bus, see page 9/28.
Expansion options
The basic hardware is expandable according to the customer’s 
particular requirements and whether the hardware is used as 
single station, server or client with the following options:
• Multi-VGA graphics card for connection of up to 4 monitors
• Process monitors (see Spage 2/17)
The multi-VGA graphics cards "2 Screens" and "4 Screens" are 
offered for multichannel operation of an OS/batch single station 
VGA graphics card, the visualization of the plant/unit can be di-
vided among up to 4 process monitors per operator station by 
using different views. These plant sections can all be operated 
using just one keyboard and one mouse. The multi-VGA graph-
ics cards are compliant with the EN 55022 and EN 50082 stan-
dards. Each card occupies one PCI slot.
Note
:
Since all messages from SIMATIC BATCH are processed in the operator 
system’s message system, the use of a signal module is only recom-
mendable with multi-function OS/batch stations (clients, single stations). 
SIMATIC BATCH clients and OS clients
Automation
systems
Batch server
OS server
Engineering
System
OS-LAN
Plant bus