Справочник Пользователя для Siemens Automobile Electronics 3RA2

Скачать
Страница из 58
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
General data
6/3
SIRIUS Innovations Supplement 2011
6
3RA2 complete units
The 3RA2 fuseless motor starters can be ordered as preassem-
bled complete units for direct-on-line starting (3RA21) or for 
reversing duty (3RA22) with screw connection. 
Control supply voltages of AC 50/60 Hz 110/120 V and 24 V DC 
are available to choose from. 
A distinction is also drawn between whether the starter is 
mounted on a 35 mm standard mounting rail, on a flat surface 
using screws, or on a 60 mm busbar system.
Accessories
As the 3RA2 fuseless motor starters are constructed from 3RV2 
motor starter protectors and 3RT2 contactors, the same acces-
sories - such as auxiliary switches, undervoltage releases or 
door-coupling rotary operating mechanisms - can be used for 
the 3RA2 fuseless motor starters as for these motor starter pro-
tectors and contactors.
In particular, certain accessories have been optimized for the 
fuseless motor starters. They include the top-connected, trans-
verse auxiliary switch on the motor starter protector, which is 
available with 1 CO contact or 1 NO contact + 1 NC contact. 
Special auxiliary switch blocks that can be snapped on from 
below are available for the contactor. These two accessories 
enable the fuseless motor starters to be wired simply without 
having to route cables through the device.
Incoming energy supply
On the whole four different infeed possibilities are available 
(see 
"3RV29 Infeed System for Motor Starters" on page 6/31)
.
Customer assembly of fuseless motor starters
While the preassembled 3RA2 can be ordered up to 32 A, com-
binations in customer assembly without link modules are also 
possible up to 40 A (approx. 25 HP/460 V).
Thanks to the SIRIUS modular system, the standard devices can 
be optimally combined in terms of both technical specifications 
and dimensions.
The fuseless motor starters can also be assembled easily by the 
customer. It is simply necessary to assemble the standard 3RV2 
motor starter protector, the 3RT2 contactor and the appropriate 
assembly kit.
For single devices and assembly kits see "Selection and order-
ing data" for 3RA21 direct-on-line starters and 3RA22 reversing 
starters.
For assembly kits for direct-on-line starting or reversing duty for 
mounting on standard mounting rails or busbars see "Selection 
and ordering data" for "Accessories".
For reversing starters size S0 it is imperative to use a standard 
mounting rail adapter in order to ensure the necessary mechan-
ical strength. A standard mounting rail adapter is not necessary 
if a busbar adapter is used.
The 3RA1 fuseless motor starters can be used for the fuseless 
motor starters between 32 A and 100 A.
The SENTRON 3VL circuit breakers and the SIRIUS 3RT contac-
tors are available for rated currents >100 A. 
Special equipment for customer assembly can be ordered if 
other rated control supply voltages are required. Assembly kits 
can be used to facilitate assembly.
Customers can also assemble tested combinations of motor 
starter protectors with solid-state controls (soft starters, solid-
state contactors) and motor starters with additional monitoring 
and control devices (3RR monitoring relays, SIMOCODE 3UF).
For the electrical and mechanical connection of protection 
equipment and controls there are preassambled assembly kits 
(link modules, wiring kits and standard mounting rail or busbar 
adapters). 
The following types of configuration are possible:
• Direct-on-line/reversing starting (see preassembled 3RA2 
combinations)
• Wye-delta starting (only customer assembly with link module)
• Solid-state/soft starting (only customer assembly with link 
module)
© Siemens AG 2011