CONNECTION SCENARIO 2 – USING A KBD4000 FOR MULTIPLEXER CONTROL
Refer to Figure 46 and the instructions that follow.
NOTE:  If you set all your cameras to Standard Coaxitron for better control on the browser, you will lose most of the KBD4000 keyboard
control functions. If you set your cameras to Extended Coaxitron, you will have all the keyboard functions but the PTZ functions on the
NET4001A will be very slow.
Figure 46.  KBD4000 Connected to a Multiplexer
Video In
Video Out
Audio Out
Audio In
COM1: RS232/485 10/100 Base-T
Ethernet
Power
100-250VAC50/60Hz 100mA
COM2: RS232
Video In
Video Out
Audio Out
Audio In
COM1: RS232/485 10/100 Base-T
Ethernet
Power
100-250VAC50/60Hz 100mA
COM2: RS232
PELCONET RECEIVER
PELCONET TRANSMITTER
9600, 8, ODD, 1
PV130
TD(A)
TD(B)
RD(A)
RD(B)
GND
+12 VDC
1
2
3
4
8
7
6
5
12 VDC
RD(A)
RD(B)
12 VAC
KBD4000
9600, 8, ODD, 1
STRAIGHT CABLE
VIDEO
ON
OFF
STRAIGHT CABLE 
COM IN 
MULTIPLEXER 
TX(-) 
TX(+) 
RX(-) 
RX(+) 
TD(A)
TD(B)
1.
Connect a PV130 converter to the COM1 port on the back of the NET4001A receiver unit. (For Interface Mode select RS232.)  The
data format must be 9600 baud, 8 data bits, odd parity, and 1 stop bit.
2.
Connect the black and white striped wire from the power supply that comes with the converter to the converter’s +12 VDC terminal
and the solid black wire to the GND terminal.
3.
Connect TD(A) on the converter to terminal 7 on the wall block. Connect TD(B) on the converter to terminal 8 on the wall block.
Connect RD(A) on the converter to terminal 2 on the wall block. Connect RD(B) on the converter to terminal 1 on the wall block.
4.
Connect a 12 VAC power supply to terminals 3 and 4 on the wall block.
5.
Connect the wall block to the KBD4000 with an RJ-45 straight cable.
6.
Connect the monitor.
7.
Refer to Figure 44 and Figure 46. Splice the customer-supplied DB9 cable into the multiplexer wall block. Connect TX- from the
NET4001A to terminal 2 on the wall block, TX+ to terminal 1, RX- to terminal 7, and RX+ to terminal 8.
8.
Plug the DB9 cable into the COM1 port on the transmitter. (For Interface Mode select RS422/485.) The data format must be 9600, 8, odd, 1.
9.
Connect the wall block to COM IN on the multiplexer with an RJ-45 straight cable.
10. Connect MAIN video output from the multiplexer to the transmitter.