  MACH®  Series
 
Gas-Fired Boiler 
Installation 
 
 
Page  25 
This port is located on the upstream side of the valve 
body for measuring supply pressure.  (See figure 
below.)   
 
 
 
 
Gas Pressure Test Port 
 
The supply pressure during main burner operation 
must be greater than the minimum indicated on the 
rating plate (3.5". W.C. for natural gas, 7" W.C. for 
propane).   
 
3.12.3  Air Flow Adjustments 
 
The air flow is pre-set at the factory prior to shipment.  
In unusual situations the air/gas ratio may have to be 
adjusted to obtain proper combustion readings for 
specific local conditions.  
Combustion measurement instrumentation must be 
used to adjust the boiler for local conditions (See 
instructions below).  Adjust the carbon dioxide (CO
2
or oxygen (O
2
) reading to achieve conditions as listed 
in the following Table 3-1.   
 
3.12.4  Gas Valve Setup and Adjustment 
Note:    Verify gas pressure at inlet to boiler is in 
accordance with Table 3-1 below.  Gas flow is 
dependent primarily on fan speed not upstream gas 
pressure.  When set up for natural gas operation, the 
boiler is capable of operating with gas supply pressure 
as low as 3.5” W C.  
Boiler Test Mode:   
The test mode should be used when checking and 
setting the gas safety shut off / control valves on the 
MACH Series  boilers.  In this mode an automatic 
heat request is simulated as follows:  
 
 
Test Mode High:  
Simultaneously pressing the “Mode” button and the 
“+” button for 3 seconds activates the “Test Mode 
High” function to drive the boiler output to 
maximum.  The display will blink and indicate “H” in 
the first digit of the display to indicate the boiler is 
being driven to the maximum output rating.  This test 
mode will automatically terminate after 15 minutes or 
can be terminated from the control/display panel by 
simultaneously pressing the “+” and “-“ buttons for 
three seconds. 
 
 
Test Mode Low:  
Simultaneously pressing the “Mode” button and the   
“-” button for 3 seconds activates the “Test Mode 
Low” function to drive the boiler output to minimum.  
The display will blink and indicate “L” in the first 
digit of the display to indicate the boiler is being 
driven to the minimum output rating.  This test mode 
will automatically terminate after 15 minutes or can 
be terminated from the control/display panel by 
simultaneously pressing the “+” and “-“  buttons for 
three seconds. 
MACH C300 & C450  
Required Tools: 
2 mm hex wrench 
Slotted screwdriver 
Combustion analyzer 
 
The MACH  C300 and C450 boilers are equipped 
with two combined gas/air control and gas safety shut 
off  control valves.  The valves function in parallel 
with the variable speed combustion blower to supply 
the correct gas air ratio for optimum performance and 
efficiency.  The combustion blower speed is 
controlled automatically and determines the amount 
of negative pressure felt at the gas safety shut off / 
control valves.  The gas valve servo regulators adjust 
gas flow for each valve to maintain zero pressure at 
the outlet nozzle of the associated valves. 
Test Port