JKSSS+ Series - 37
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
5.1.3 Phase and Ground Settings (Setpoint Page 3)
* Ground fault option must be installed.
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range
Section
Imbalance Alarm Level
15% FLA
5-30 %, Off
Imbalance Alarm Delay
1.5 sec
1.0-20.0 sec
Imbalance Trip Level
20%
5-30 %, Off
Imbalance Trip Delay
2.0 sec
1.0-20.0 sec
Undercurrent Alarm Level
Off
10-90 %, Off
Undercurrent Alarm Delay
2.0 sec
1.0-60.0 sec
Overcurrent Alarm Level
Off
100-300 %, Off
Overcurrent Alarm Delay
2.0 sec
1.0-20.0 sec
Overcurrent Trip Level
Off
100-300 %, Off
Overcurrent Trip Delay
2.0 sec
1.0-20.0 sec
Phase Loss Trip
Enabled
Enabled or Disabled
Phase Loss Trip Delay
0.1 sec
0-20.0 sec
Phase Rotation Detection
ABC
ABC, ACB or Disabled
Phase Rotation Trip Delay
1.0 sec
1.0 - 20.0 sec
*Ground Fault Alarm Level
Off
5-90 %, Off
*Ground Fault Alarm Delay
0.1 sec
0.1-20.0 sec
*Ground Fault Loset Trip Level
Off
5-90 %, Off
*Ground Fault Loset Trip Delay
0.5 sec
0.1-20 sec
*Ground Fault Hiset Trip Level
Off
5-90 %, Off
*Ground Fault Hiset Trip Delay
0.008 sec
0.008-0.250 sec
Overvoltage Alarm Level
Off
5 -30%, Off
Overvoltage Alarm Delay
1.0 sec
1.0-30.0 sec
Overvoltage Trip Level
10%
5-30%, Off
Overvoltage Trip Delay
2.0 sec
1.0-30.0 sec
Undervoltage Alarm Level
Off
5-30%, Off
Undervoltage Alarm Delay
1.0 sec
1.0-30.0 sec
Undervoltage Trip Level
15%
5-30%, Off
Undervoltage Trip Delay
2.0 sec
1.0-30.0 sec
Line Frequency Trip Window
Disabled
0-6 Hz, Disabled
Line Frequency Trip Delay
1.0 sec
1.0-20.0 sec
P/F Lead P/F Alarm
Off
0.1-1.00, Off
P/F Lead Alarm Delay
1.0 sec
1-120 sec
P/F Lead P/F Trip
Off
.01-1.00, Off
P/F Lead Trip Delay
1.0 sec
1-120 sec
P/F Lag P/F Alarm
Off
.01-1.00, Off
P/F Lag Alarm Delay
1.0 sec
1-120 sec
P/F Lag P/F Trip
Off
.01-1.00, Off
P/F Lag Trip Delay
1.0 sec
1-120 sec
Power Demand Period
10 min
1 - 60 min
KW Demand Alarm Pickup
Off KW
Off, 1-100000
KVA Demand Alarm Pickup
Off KVA
Off, 1-100000
KVAR Demand Alarm Pickup
Off KVAR
Off, 1-100000
Amps Demand Alarm Pickup
Off Amps
Off, 1-100000
Page 
3
Phase and Ground Settings
Level 
2
Password Protection
SP3.1
SP3.2
SP3.3
SP3.4
SP3.5
SP3.6
SP3.7
SP3.8
SP3.11
SP3.12
SP3.18
SP3.20
SP3.13
SP3.14
SP3.15
SP3.9
SP3.10
SP3.19
SP3.17
SP3.16