JKSSS+ Series - 61
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
SP.7 Custom Acceleration Curve (Setpoint Page 7)
(Security Level: 3)
SP7.1 Setpoint Page 7 allows the user to custom design 
the acceleration curve (start curve) to the specific 
application. The user can custom design up to 
three different curves in the soft starter. Only one 
curve can be active (enabled) at a time. Each of 
the three curves has eight voltage levels, with 
corresponding ramp times and a current limit 
setting.  
 
  Note: Each successive voltage level must be 
programmed to a voltage level equal to or greater 
than the previous level. All eight levels of voltages 
must be programmed and the eighth level has 
been preset at 100%.
  If Custom Accel Curve has been set to curve A, B 
or C on this page, the soft starter will override the 
Start Control Mode selected in Setpoint Page 2, 
(even if Start Control Mode in Setpoint Page 2 has 
not been set to Custom Accel Curve).  
 
  Note: Setpoint Page 7 has a security level 3 
requirement.
CURVE C VOLTAGE
LEVEL 6:  67%
CURVE C VOLTAGE
LEVEL 7:  82%
CURVE C RAMP
TIME 7: 2 SEC.
CURVE C VOLTAGE
LEVEL 8:  100%
CURVE C RAMP
TIME 6: 2 SEC.
CURVE C CURRENT
LIMIT:  350% FLA
CURVE C RAMP
TIME 8: 2 SEC.
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 200 - 600%
Increments of 10
CUSTOM CURVE C