 Installation Orientation
Install the Inverter vertically so as not to reduce the cooling effect. When installing the Inverter,
always provide the following installation space to allow normal heat dissipation.
Fig 2  Installation space
„
 Installation of Inverters and EMC filters
For an EMC rules compliant installation
consider the following points:
Use a line filter.
Use shielded motor cables.
Mount the inverter and filter on a
grounded cunductive plate.
Remove any paint or dirt before mount-
ing the parts in order to reach the low-
est possible grounding impedance.
Fig 3  EMC filter installation
IMPORTANT
1. The same space is required horizontally and vertically for IP00, IP20 and NEMA 1 Inverters.
2. Always remove the top protection cover after installing an Inverter with an output of 18.5 kW or less in a
panel.
Always provide enough space for suspension eye bolts and the main circuit lines when installing an
Inverter with an output of 22 kW or more in a panel.
A
B
Horizont
a
S
p
a
ce
50mm
min.
3
0mm min.
3
0mm min.
120mm min.
Air
Air
Vertic
a
S
p
a
ce
A
B
200V class inverter, 0.55 to 90 kW
400V class inverter, 0.55 to 132 kW
50 mm
120 mm
200V class inverter, 110 kW
400V class inverter, 160 to 220 kW
120 mm 120 mm
400V class inverter, 300 kW
300 mm 300 mm
Gro
u
nd Bond
s
Remove 
a
ny p
a
int
!
PE
L1
L2
L
3
PE
Line
Filter
Gro
u
nd Bond
s
Remove 
a
ny p
a
int
!
Lo
a
d
GND L1
L2
L
3
GND
U
V
W
M
~3
S
creened 
Motor c
ab
le
C
ab
le Lenght
as
 
s
hort 
as
 po
ss
i
b
le
Gro
u
nded 
Met
a
l Pl
a
te
Inverter