Status
LED
Status LED 
Description
Status LED Troubleshooting Information
Green 
“POWER”
Module has 
power
Supply voltage is present at module terminals
Red “TRIP”
Thermostat 
demand signal 
Y is present, but 
compressor is not 
running
• 
Compressor protector is open
• 
Check for high head pressure
• 
Check compressor supply voltage
• 
Outdoor unit power disconnect is open
• 
Compressor circuit breaker or fuse(s) is open
• 
Broken wire or connector is not making contact
• 
Low pressure switch open if present in system
• 
Compressor contactor has failed open
Yellow “ALERT” 
Flash Code 1
Long Run Time 
Compressor is 
running extremely 
long run cycles
• 
Low refrigerant charge
• 
Evaporator blower is not running
 
Check blower relay coil and contacts
 
Check blower motor capacitor
 
Check blower motor for failure or blockage
 
Check evaporator blower wiring and connectors
 
Check indoor blower control board
 
Check thermostat wiring for open circuit
• 
Evaporator coil is frozen
 
Check for low suction pressure
 
Check for excessively low thermostat setting
 
Check evaporator airfl ow (coil blockages or return airfi lter)
 
Check ductwork or registers for blockage
• 
Faulty metering device
 
Check TXV bulb installation (size, location and contact)
 
Check if TXV/fi xed orifi ce is stuck closed or defective
• 
Condenser coil is dirty
• 
Liquid line restriction (fi lter drier blocked if present in system)
• 
Thermostat is malfunctioning
 
Solenoid plug not connected
 
Y2 not wired at Comfort Alert
 
Check thermostat sub-base or wiring for short circuit
 
Check thermostat installation (location, level)
• 
Comfort Alert failure
Yellow “ALERT” 
Flash Code 2
System Pressure 
Trip
• 
High head pressure
 
Check high pressure switch if present in system
 
Check if system is overcharged with refrigerant
 
Check for non-condensable in system
Discharge or 
suction
• 
Condenser coil poor air circulation (dirty, blocked, damaged)
pressure out of 
limits
• 
Condenser fan is not running
 
Check fan capacitor
 
Check fan wiring and connectors
 
Check fan motor for failure or blockage
compressor 
overloaded
• 
Return air duct has substantial leakage
• 
If low pressure switch present in system, check Flash Code 
1 information
TROUBLESHOOTING
Table 4. LED Diagnostics